Description of the blocks
4.4 Block for MMMeas measured value function
SIMOCODE pro PCS 7 Library V9.0
164
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.4.8
Enabled operations
The operator permissions for control commands are configured in the
OS_Perm
structured
parameters. These are transferred to WinCC via the
OS_PermOut
and
OS_PermLog
parameters.
The operator parameters are controlled via the FBs in CFC.
The activated parameter allows the operator to enter the desired commands.
The operator permissions control operation only in the faceplate.
Table 4- 72 Operator permissions – MMMeas
OS_Perm
bit
OS_PermOut
bit
OS_PermLog
bit
Description
0
0
0
Reserved
1
1
1
1 = Operator is permitted to change to ON
mode
2
2
2
Reserved
3
3
3
1 = Operator is permitted to change to "Out
of service" (Oos) mode
4...20
4...20
4...20
Reserved
21
21
21
1 = Operator is permitted to read data from
the device
22
22
22
1 = Operator is permitted to write at output
AM
23
23
23
1 = Operator is permitted to write at output
AM2
24…31
24…31
24…31
Reserved
OS_PermOut
contains the release information of all parameters.
OS_PermLog
contains the release based on the current modes.