Description of the blocks
4.4 Block for MMMeas measured value function
SIMOCODE pro PCS 7 Library V9.0
160
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Table 4- 68 Assignment of PZDInxx to the feedback from SIMOCODE pro
Basic unit type
SIMOCODE pro
byte
Cyclic
send data
PZDInxx
BU 1
4–5
Values
parameterized in
SIMOCODE ES
PZDIn45
6–7
PZDIn67
8–9
PZDIn89
SIMOCODE pro
PROFINET:
BU 3
10–11
–
PZDIn10
12–13
PZDIn12
14–15
PZDIn14
16–17
PZDIn16
18–19
PZDIn18
4.4.4.3
Write analog output
The analog output can be written cyclically to the SIMOCODE pro device.
With the parameter
LiOp
, you can parameterize whether the operator-controllable input
AMOutIn
,
AM2OutIn
(LiOp = FALSE)
or the interconnectable input
AMOutLi
,
AM2OutLi
is used
(LiOp = TRUE)
.
If the interconnectable input is selected, the operator-controllable input is deactivated.
4.4.4.4
Acyclic reading
Reading the data record 94 is either triggered using the interconnectable input parameter
RdDataLi
, in the OS when selecting the faceplate, or by OS operation (
RdDataOp = 1
).
The data that is read is normalized and sent to the output parameters.
If an error occurs, the values are set to zero and the output
RdErr = 1
is set.