"Interlock active" output via the LockAct parameter
The
LockAct
parameter is always set automatically if an interlock is set in the following
parameters:
●
Intlock
●
Permit
●
Protect
●
Trip
The
LockAct = 0
parameter if the interlock is canceled and the interlocks that require
acknowledgments have been acknowledged.
You can bypass the interlock using
BypProt = 1
in local mode and during simulation. This
also makes
LockAct = 0
.
How the signal status affects the interlocks
There are three ways in which the signal status affects the interlocks:
No. Icon
Signal status
1
Simulation (16#60):
•
If the interlock signal with the status 16#60 brings about a cancela-
tion of the interlock, this is processed as a bypass of the interlock in
the block.
•
If the interlock signal with status 16#60 does not bring about a can-
celation of the interlock, this is processed in the block as simulation.
2
"bad, device-related" (16#28) or " bad, process-related" (16#00)
→ The signal status is used to activate the motor to stop.
3
–
Signal status ≠
Simulation, "bad, device-related" and " bad, process-
related"
→ No change in the block
Reference
MMRevDhl - Standard (Page 223)