![Siemens SIMOCODE pro Скачать руководство пользователя страница 89](http://html.mh-extra.com/html/siemens/simocode-pro/simocode-pro_programming-and-operating-manual_1265395089.webp)
Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
89
depending on the mode, only by the operator in manual mode or by the automatic I/Os in
automatic mode.
Resetting to manual mode is enabled with
Feature
Bit 31 (Activating reset of protection /
error in manual mode). Also refer to the Resetting the block in case of interlocks or errors
chapter.
The default setting is 0.
Bit = 0: Reset does not depend on the operating mode
Bit = 1: In manual mode, manual reset by the operator is only possible if
Feature
Bit 31 is
set, otherwise no reset is required in manual mode.
In automatic mode, reset can only be made with automatic I/Os, regardless of
Feature
Bit 31.
This is performed either with a 0-1 edge transition at the
RstLi
input or, when
Feature
Bit 9 is
set, with a 0-1 edge transition at the automatic inputs, for example
OpenAut
,
CloseAut
.
Note
Rapid stop is unlocked for all operating modes using the "Reset" button in the faceplate
(
RstOp = 1
); in CFC it is unlocked using the
RstLi = 1
input parameter.
Note
The local operating mode does not depend on this
Feature
Bit and has a separate reset
mechanism.
Resetting the dosing mode depending on the operating mode (dosing blocks)
This feature bit can also be used to set whether or not the reset of the dosing quantity is
dependent on the operating mode.
The default setting is 0.
Bit = 0: Reset does not depend on the operating mode.
Bit = 1: In manual mode, only a manual reset by the operator is possible at the input
RstDQ_Op
. In automatic mode, a reset is only possible by a 0-1 edge transition at the input
RstDQ_Li
.
Note
The operating mode Local is independent of this feature bit. The dosing quantity can be
reset by the operator at the input
RstDQ_Op
or via a 0-1 edge transition at the input
RstDQ_Li
.