Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
197
4.7
MMRevDhl motor block
4.7.1
Application
4.7.1.1
Description of MMRevDhl
Purpose of the block
The MMRevDhl motor block controls the operation of a Dahlander High Feature reversing
starter.
The following commands are available in automatic mode and in manual mode:
●
Forward
●
Fast Forward
●
Reverse
●
Fast Reverse
●
Stop
Use
In AUTO mode, the commands can be given based on the
Feature.Bit4
: 0 = pushbutton
mode, 1 = switch mode.
The commands for starting and stopping the motor (
FwdMan, FFwdMan, StopMan, RevMan,
FRevMan
) are reset at the end of the execution cycle of the block because the commands are
pulse signals in manual operation.
At the
ErrorNum
parameter, error “Invalid signal status” is indicated if
FwdAut = 1
and
StopAut = 1
, provided that
Feature.Bit4 = 0
.
Block icons and faceplates
The MMRevDhl motor block can be indicated via 2 block icons.
The commands can be issued from the faceplate if the operator permission has been
programmed at the
OS_Perm
parameter.