Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
91
4.1.10.24
Suppression of single alarm message
Feature Bit
MMOprtn: Number of the
Feature
bit 0 to bit 14
MMStat: Number of the
Feature
bit 10 to bit 17
MMMeas: Number of the
Feature
bit 10 to bit 17
Suppression of single alarm message
Feature bit purpose
To determine whether the alarm message described at the feature bit of the block is to be
suppressed.
Bit = 0: Single alarm message is not suppressed.
Bit = 1: Single alarm message is suppressed.
Note
Alarm messages can be suppressed completely or separately using different feature bits
(Suppression of all messages/ Suppression of single alarm message).
4.1.10.25
Resetting control in case of invalid command
Number of the
Feature2
bit: 3
Feature2 bit purpose
To define the control priority in the event of an invalid input command.
The default setting is 0.
Bit = 0: In the event of an invalid input command, the control output is retained.
Bit = 1: In the event of an invalid input command, the control output switches to the "neutral
position".
4.1.10.26
Setting switch or button mode for local commands
Number of the
Feature2
bit: 4
Feature2 bit purpose
To determine whether a separate interconnectable 1-active control input has to be used for
every local command of the block or two local commands are assigned to a control input.