Result
When the firmware is successfully loaded a dialog is displayed . Confirm the dialog with "OK".
The device is restarted.
In "Information" > "Versions" there is the additional entry "Firmware_Running".
Firmware_Running shows the version of the current firmware. Firmware shows the firmware
version stored after loading the firmware.
5.2
Firmware update using WBM not possible
Cause
If there is a power failure during the firmware update, it is possible that the device is no longer
accessible using WBM and CLI.
Requirement
● The PC is connected to the device via the interfaces (P1 - P4).
● A TFTP client is installed on the PC and the firmware file exists.
Solution
You can then also transfer firmware to the device using TFTP.
Follow the steps below to load new firmware using TFTP:
1. Now press the SET button.
2. Hold down the button until the red fault LED (F) starts to flash after approximately 3 seconds.
Note
If you hold down the SET button for approximately 10 seconds, the device is reset to its
factory settings and can be reached with the IP address 192.168.1.1.
Upkeep and maintenance
5.2 Firmware update using WBM not possible
SCALANCE S615 Web Based Management
300
Configuration Manual, 11/2019, C79000-G8976-C388-08
Содержание SIMATIC NET SCALANCE S615
Страница 12: ...Table of contents SCALANCE S615 Web Based Management 12 Configuration Manual 11 2019 C79000 G8976 C388 08 ...
Страница 24: ...Description 1 7 PLUG SCALANCE S615 Web Based Management 24 Configuration Manual 11 2019 C79000 G8976 C388 08 ...
Страница 316: ...Appendix A A 3 Syslog messages SCALANCE S615 Web Based Management 316 Configuration Manual 11 2019 C79000 G8976 C388 08 ...
Страница 320: ...Index SCALANCE S615 Web Based Management 320 Configuration Manual 11 2019 C79000 G8976 C388 08 ...