Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
173
Number Effect/cause
Remedy
290073 An action (e.g. saving a data record) failed due to
an unknown error.
The error corresponds to the status alarm
IDS_OUT_CMD_EXE_ERR in the large recipe
view.
-
290074 While saving, it was detected that a data record
with the specified number already exists but under
another name.
Overwrite the data record, change the data record
number or cancel the action.
290075 A data record with this name already exists.
The data record is not saved.
Please select a different data record name.
300000 Faulty configuration of process monitoring (e.g.
using PDiag or S7-Graph): More alarms are
queued than specified in the specifications of the
CPU. No further ALARM_S alarms can be
managed by the PLC and reported to the HMI
devices.
Change the controller configuration.
300001 ALARM_S is not registered on this controller.
Select a controller that supports the ALARM_S service.
310000 An attempt is being made to print too many reports
in parallel.
Only one log file can be output to the printer at a
given time; the print job is therefore rejected.
Wait until the previous active log was printed.
Repeat the print job if necessary.
310001 An error occurred on triggering the printer. The
report is either not printed or printed with errors.
Evaluate the additional system alarms related to this
alarm.
Repeat the print job if necessary.
320000 The movements have already been indicated by
another device.
The movements can no longer be controlled.
Deselect the movements on the other display units and
select the motion control screen on the required display
unit.
320001 The network is too complex.
The faulty addresses cannot be indicated.
View the network in STL.
320002 No diagnostics alarm selected.
The unit belonging to the alarm could not be
selected.
Select a diagnostics alarm from the ZP_ALARM alarm
screen.
320003 No alarms exists for the selected unit. The detail
view cannot visualize any networks.
Select the defective unit from the overview screen.
320004 The required signal states could not be read by the
PLC. The faulty addresses cannot be found.
Check the consistency between the configuration on the
display unit and the PLC program.
320005 The project contains ProAgent elements which are
not installed. ProAgent diagnostic functions cannot
be performed.
In order to run the project, install the optional ProAgent
package.
320006 You have attempted to execute a function which is
not supported in the current constellation.
Check the type of the selected unit.
320007 No error-triggering addresses were found on the
networks.
ProAgent cannot indicate any faulty addresses.
Switch the detail screen to STL layout mode and check
the status of the addresses and exclusion addresses.
320008 The diagnostic data stored in the configuration are
not synchronized with those in the PLC.
ProAgent can only indicate the diagnostic units.
Download the project to the HMI device again.