Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
167
Number Effect/cause
Remedy
230303 The remote server is not running on the addressed
computer.
Wrong server address.
The attempt to connect failed
Check the configured server address.
Check if the remote server is running on the target
computer.
230304 The remote server on the addressed computer is
incompatible to VNCOCX.
The attempt to connect failed.
Use a compatible remote server.
230305 The authentication has failed because the
password is incorrect.
The attempt to connect failed.
Configure the correct password.
230306 Error in the connection to the remote server. This
may occur as a result of network problems.
The attempt to connect failed.
Check if
•
the bus cable is plugged in
•
there are network problems
230307 The connection to the remote server was shut
down because
•
the remote server was shut down, or
•
the user instructed the server to close all
connections.
The connection is closed.
-
230308 This alarm provides information on the connection
status.
An attempt is made to connect.
-
240000 WinCC flexible Runtime is operating in demo mode.
You have no authorization or your authorization is
corrupted.
Install the authorization.
240001 WinCC flexible Runtime is operating in demo mode.
Too many tags are configured for the installed
version.
Load an adequate authorization / powerpack.
240002 WinCC flexible Runtime is operating with a time-
limited emergency authorization.
Restore the full authorization.
240003 Authorization failed.
Without authorization, WinCC will run in demo
mode.
Restart WinCC flexible Runtime or reinstall it.
240004 Error while reading the emergency authorization.
WinCC flexible Runtime is operating in demo mode.
Restart WinCC flexible Runtime, install the authorization
or repair the authorization (see Commissioning
Instructions Software Protection).
250000 The tag in the specified line in "Status force" is not
updated because the address configured for this
tag is not available.
Check the set address and then verify that the address is
set up in the controller.
250001 The tag in the specified line in "Status force" is not
updated because the controller type configured for
this tag does not exist.
Check the set address.
250002 The tag in the specified line in "Status force" is not
updated because it is not possible to map the
controller type in the tag type.
Check the set address.
250003 An attempt to connect to the PLC failed. The tags
are not updated.
Check the connection to the PLC. Check that the
controller is switched on and is online.
260000 An unknown user or an unknown password has
been entered in the system.
The current user is logged off from the system.
Log on to the system as a user with a valid password.