Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
153
Number Effect/cause
Remedy
40011 The system function could not be executed since
the parameters could not be converted to a
common tag type.
Check the parameter types in the configuration.
50000 The HMI device is receiving data faster than it is
capable of processing. Therefore, no further data is
accepted until all current data have been
processed. Data exchange then resumes.
-
50001 Data exchange has been resumed.
-
60000 This alarm is generated by the
“DisplaySystemAlarms” function. The text to be
displayed is transferred to the function as a
parameter.
-
60010 The file could not be copied in the direction defined
because one of the two files is currently open or the
source/target path is not available.
It is possible that the Windows user has no access
rights to one of the two files.
Restart the system function or check the paths of the
source/target files. Using Windows NT/2000/XP: The user
executing WinCC flexible Runtime must be granted
access rights for the files.
60011 An attempt was made to copy a file to itself.
It is possible that the Windows user has no access
rights to one of the two files.
Check the path of the source/target file.
Using Windows NT/2000/XP with NTFS: The user
executing WinCC flexible Runtime must be granted
access rights for the files.
70010 The application could not be started because it
could not be found in the path specified or there is
insufficient memory space.
Check if the application exists in the specified path or
close other applications.
70011 The system time could not be modified.
The error alarm only appears in connection with
area pointer "Date/time PC". Possible causes:
•
An invalid time was transferred in the job
mailbox.
•
The Windows user has no right to modify the
system time.
If the first parameter in the system alarm is
displayed with the value 13, the second parameter
indicates the byte containing the incorrect value.
Check the time which is to be set.
Using Windows NT/2000/XP: The user executing WinCC
flexible Runtime must be granted the right to change the
system time of the operating system.
70012 An error occurred when executing the function
"StopRuntime" with the option "Runtime and
operating system".
Windows and WinCC flexible Runtime are not
closed.
One possible cause is that other programs cannot
be closed.
Close all programs currently running.
Then close Windows.
70013 The system time could not be modified because an
invalid value was entered. Incorrect separators may
have been used.
Check the time which is to be set.
70014 The system time could not be modified. Possible
causes:
•
An invalid time was transferred.
•
The Windows user has no right to modify the
system time.
•
Windows rejects the setting request.
Check the time which is to be set.
Using Windows NT/2000/XP: The user executing WinCC
flexible Runtime must be granted the right to change the
system time of the operating system.