Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
159
Number Effect/cause
Remedy
130005 The file is read only. The operation is canceled.
Check if access has been made to the correct file. Edit
the file attributes if necessary.
130006 Access to file failed. The operation is canceled.
Check, for example, if
•
the correct file is being accessed
•
the file exists
•
another action is preventing simultaneous access to
the file
130007 The network connection is interrupted.
Data records cannot be saved or read over the
network connection.
Check the network connection and eliminate the cause of
error.
130008 The storage card is not available.
Data records cannot be saved to / read from the
storage card.
Insert the storage card.
130009 The specified folder does not exist on the storage
card.
Any files saved to this directory are not backed up
when you switch off the HMI device.
Insert the storage card.
130010 The maximum nesting depth can be exhausted
when, for example, a value change in a script
results in the call of another script and the second
script in turn has a value change that results in the
call of yet a further script etc.
The configured functionality is not supported.
Check the configuration.
140000 An online connection to the controller is
established.
-
140001 The online connection to the controller was shut
down.
-
140003 No tag updating or writing is executed.
Check the connection and if the controller is switched on.
Check the parameter definitions in the Control Panel
using "Set PG/PC interface".
Restart the system.
140004 No tag update or write operations are executed
because the access point or the module
configuration is faulty.
Verify the connection and check if the controller is
switched on.
Check the access point or the module configuration (MPI,
PPI, PROFIBUS) in the Control Panel with "Set PG/PC
interface".
Restart the system.
140005 No tag updating or writing is executed because the
HMI device address is incorrect (possibly too high).
Use a different HMI device address.
Verify the connection and check ifthe controller is
switched on.
Check the parameter definitions in the Control Panel
using "Set PG/PC interface".
Restart the system.
140006 No tag updating or writing is executed because the
baud rate is incorrect.
Select a different baud rate in WinCC flexible (according
to module, profile, communication peer, etc.).