Simatic 505 SoftShop
To import and/or configure data from the COM PROFIBUS software,
you must be running 505 SoftShop, and the binary file (with its .2BF
extension) that you created with COM PROFIBUS must be in a known
location. Follow the steps below to execute:
1.
Select PLC Configuration from the PLC Utilities menu.
Result: The PLC Configuration dialog box appears (Figure 5.2).
2.
Select the
Profibus I/O
button under I/O configuration on the
PLC Configuration dialog box.
Result: The Profibus-DP I/O dialog box appears.
The Profibus-DP I/O dialog box dialog box Slave Status window shows
the following information:
1.
Slave numbers programmed from 1 to 112 or 1 to 32 for the
545L.
2.
The Enabled state.
3.
The Assigned state:
•
Yes, if all slave modules have I/O addresses assigned to
them.
•
No, if some or all slave modules do not have I/O addresses
assigned to them.
4.
Online:
•
Yes, if in operate mode and PROFIBUS slave is connected.
•
No, if in stop mode or PROFIBUS slave is not connected.
5.
Status:
•
Match, if the configuration and the I/O assignments match
the online controller or the offline program.
•
*Match, if the configuration matches the online controller or
the offline program and the I/O assignments do not match
online controller or the offline program.
•
New, if the slave is programmed in the .2bf file but not in
the online controller or the offline program.
•
Mismatch, if the slave number exists in the .2bf file and in
the online controller or the offline program, but has been
configured differently.
•
Delete, if the slave is in the online controller or the offline
program, but not in the .2bf file. When the program is
written to the online controller or the offline program, the
slave will be deleted.
The Profibus-DP I/O dialog box allows you to execute the following
functions:
•
Merge.
•
Write All.
•
Write Slave(s).
•
Enable Slaves.
•
Disable Slaves.
•
Delete all slaves.
•
Edit slave.
•
Profibus operations (online only).