Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
215
DC8-001-2.09, Edition 08.2016
5.1.9.5.5 Command Output
Standard Command Output
For the output of standard commands (
OC
) an appropriate digital output module must be
equipped, and the DO signals to be used must be configured.
Common Settings:
•
Monitor pulse duration
The command output time defines how long the actuator is actuated. The output time can
be set for each data point with the parameter
output_t
.
•
Monitor return information
The return information monitoring is used to limit the command output to the output time
required by the process. The return information monitoring can be activated for each data
point with parameter
RS_Mon_t
.
•
Procedure for the command transmission according to IEC 60870-5-101/104
The procedure for "direct command" is set by means of the parameter
select_execute_t
=
0
.
The procedure for "select and execute command" is set by means of the parameter
select_execute_t
>
0
. The parameterized value specifies, within which time the execute
command must be received following the selection command.
You find the exact information on the command output in the manual
SICAM RTUs Common
Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Pulse Com-
mands", section "Functions Independent on the Hardware of the System Element"
.
Assignment Return Information to Pulse Command
This function coordinates binary information and pulse commands that are acquired or output
on SICAM TM I/O modules. You find the exact information thereto in the manual
SICAM RTUs
Common Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Return
Information to Pulse Command Assignment"
.
•
Parameter-settable assignment
The assignment of an information (DI signal) to a pulse command (DO signal) is adjustable
through the 5-digit address of the return information (parameters
RS_Image_CASDU1
,
RS_Image_CASDU2
,
RS_Image_IOA1
,
RS_Image_IOA2
,
RS_Image_IOA3
).
No assignment takes place if the parameters are set to the value
255
(default value) the
target device utilizes the fixed assignment.
•
Predefined assignment
If the equipped sequence of I/O modules is suitable, an information is assigned automati-
cally to a command. Otherwise no assignment takes place. You find the exact assignment
in the following table.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...