Engineering via SICAM WEB
192
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.9.4.3 Parameters with Assignment on the DO Module
This data can be changed – for each category – in the table for the signal generation:
Processing type
Parameter
Meaning
DO_DC_1,5POL - double
command output 1,5-pole
Retry_suppression_T
Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
output_t_0
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
select_execute_t
Max. time between select and execute (in se-
conds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3
Sync_t_0
Within this time (in sec) the interlock enabling
must occur on the command. 0=no
syncronisation over interlocking
0.1 to 6553.5
RS_Mon_t
Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command_prolong_t
Command prolongation time in seconds (S)
0.01 to 327.67
output_t_1
Command output time in seconds (S). Atten-
tion: The time comes into effect only, if in the
message is not defined any time.
0.01 to 327.67
Sync_t_1
Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_outp_same_state_0
Selection of command output and command
confirmation, if return state is already end po-
sition before output.
Attention: only active if RS_mon_t
≠
0.
Sync_Input_t_0
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0=no syncronisation over syncronisation input.
Attention: Function only active if sync_t = 0.
0.1 to 6553.5
1_out_of_n_t_0
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
RS_outp_same_state_1
Selection of command output and command
confirmation, if return state is already end po-
sition before output.
Attention: only active if RS_mon_t
≠
0
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...