Engineering via SICAM WEB
198
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Processing type
Parameter
Meaning
RS_Image_TI
Type identifier of corresponding return state
information (S)
•
Single-point information
•
D.-point information
Term_with_Conf
Sending of termination immediately after
sending of confirmation (S)
NO/YES
Output_t_0
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
termination_t_0
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
RS_react_t_0
Information reaction time (S)
Pulse command: 0 .. time appropriate to out-
put time
Persistent command: 0 .. time appropriate to
termination time
0 to 6553.5
Output_t_1
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
termination_t_1
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
RS_react_t_1
Information reaction time (S)
Pulse command: 0 .. time appropriate to out-
put time
Persistent command: 0 .. time appropriate to
termination time
0 to 6553.5
DO_SC_1,5POL – single
command output 1,5-pole
Retry_suppression_T
Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
Output_t
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
select_execute_t
Max. time between select and execute (in se-
conds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3
Sync_t
Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_Mon_t
Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command_prolong_t
Command prolongation time in seconds (S)
0.01 to 327.67
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...