Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
177
DC8-001-2.09, Edition 08.2016
Category
Parameter
Meaning
MV_CASDU1
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
MV_CASDU2
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
MV_IOA1
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
MV_IOA2
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
MV_IOA3
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
MV_TI
Type identification according to
IEC 60870-5-101/104
Process control
pc_Event
The data point is displayed in the event list
pc_Process_Text
The data point is displayed with this name
(max. 13 characters)
pc_State_TextOn
The state ON for single or double point infor-
mation is displayed with this name (max.
6 characters)
pc_State_TextOff
The state OFF for single or double point in-
formation is displayed with this name (max.
6 characters)
pc_State_TextFlt
The state faulty position for double point in-
formation is displayed with this name (max.
6 characters)
pc_State_TextInt
The state intermediate position for double
point information is displayed with this name
(max. 6 characters)
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
Process value analog
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
pva_Process_Text
The data point is displayed with this name
(max. 13 characters)
pva_Process_GroupNbr
The data point is displayed in the cockpit in
this group (1…32)
pva_Process_GroupPos
The data point is displayed in the cockpit on
this position (1…256)
pva_X_0%
Value adaptation: Lower limit of the used
measuring range in the external (protocol
specific) format. The corresponding internal
value is defined at Y_0%.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...