Engineering via SICAM WEB
202
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Processing type
Parameter
Meaning
RS_Image
Parameter works only with ACP 1703 platform
DO_SI – digital output –
single-point information
receive_format
Source of datapoint
Fail_behav
Behavior at failure
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE
Source identification supplementary system
element
DO_SX – single-point
information and single
command output
receive_format
Source of datapoint
Fail_behav
Behavior at failure
•
keep
•
terminate
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE
Source identification supplementary system
element
select_execute_t
Max. time between select and execute (in se-
conds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0 to 6553.5
RS_Image_CASDU1
Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_CASDU2
Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA1
Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA2
Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA3
Address of corresponding return state infor-
mation (S)
0 to 255
Term_with_Conf
Sending of termination immediately after
sending of confirmation (S)
NO/YES
Output_t
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
termination_t
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
RS_react_t
Information reaction time (S)
Pulse command: 0 .. time appropriate to out-
put time
Persisitent command: 0 .. time appropriate to
termination time
0 to 6553.5
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...