Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
179
DC8-001-2.09, Edition 08.2016
Category
Parameter
Meaning
Station
•
0…99 = station number
•
125 = to all stations
•
255 = not used
Additional_parameter_(PRE)
0...65535 = meaning for each function de-
fined by the PRE firmware
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
104-Address
TI
Type identification according to
IEC 60870-5-101/104
•
Single-point information
•
Single command
Protocol element return
information message
Return_information_function_
(PRE)
PRE_(RM)
Protocol element number (0…3)
Station
Station number (selective 0...99; to all sta-
tions; station not used)
Redundancy control
message
Control_function_(RED)
•
User priority
•
A/P-control
•
Key switch
•
Listening mode-control
•
A/P-control with failed SCA-RS
•
Switch-over disabled
Failure_behavior_(RED)
•
Terminate binary information
•
Maintain status
BSE_(RED)
Basic system element
PRE_(RED)
Protocol element number
Priority_(RED)
Priority 0 (lowest)…priority 14 (highest)
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
Redundancy return in-
formation message
Return_information_function_
(RED)
•
Redundancy state
•
Switchover runs at a global switchover
•
Keyswitch of the SCA-RS: system A active
•
Keyswitch of the SCA-RS: automatic
•
Keyswitch of the SCA-RS: system B active
•
Listening mode
BSE_(RED)
Basic system element
PRE_(RED)
Protocol element number
Selective data flow rout-
ing
PRE
Protocol element number (0…3)
Station
0…99 = selective station
unused = single-point-PRE or multi-point-
PRE to all remote stations
Data_class
•
Data class 1
•
Data class 2
Periodical transfer
Selection periodical level or no periodical
transfer
Event_data
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...