Processing type
Parameter
Meaning
DI_SI – single-point in-
formation input
Inversion
Inversion (S)
NO/YES
block
Blocking (= not used) (S)
NO/YES
Flutt_dp_qds
Datapoint quality discriptor for fluttery binary
information
BL/IV
input function
Functionality of the binary input. This parame-
terization permits to disable the information
input for revision handling.
SVM_monitoring
Power monitoring. The sensor voltage is moni-
tored by an own power monitoring input (S).
NO/YES
Flutt_Number
Number of transients for flutter suppression
(S)
SW_Filter_t
Software filter-time in s (S)
Flutt_t
Flutter time in seconds.
0 = no fluttersuppression (S)
0.1 to 6553.5
State_of_flutter_information
Information state in message with BL bit
Delay_t
Delaytime from ON singlepoint information in
seconds
0 to 16000
Moduleselection_SVM_
monitoring
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI module.
Flutt_t_stable
Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5
DI_CV – count pulse ac-
quisition
message_blocking_t
Message blocking time in seconds. During this
time period, identical messages will be dis-
carded without error information.
0.1 to 6553.5
interval_time_0
Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
interval_time_1
Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
Inversion
Inversion (S)
NO/YES
block
Blocking (= not used) (S)
NO/YES
Type
Conditioned value type (S)
•
latched absolute value
•
latched relative value
SVM_monitoring
Power monitoring. The sensor voltage is moni-
tored by an own power monitoring input (S)
transm_prompting
Transmission prompting. The initiating for the
transfer of the latched count can happen
through a counter interrogation message
(group), through adjustable intervals, or
through the function diagramm. (S)
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...