Engineering via SICAM WEB
212
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.9.5.1 Binary Information Acquisition
For the acquisition of single-point or double-point information items, an appropriate digital in-
put module must be equipped, and the DI signals to be used must be configured.
Power Monitoring
You can activate the power monitoring for digital inputs jeweils with the parameter
SVM_monitoring
. The monitoring takes place by groups:
Group 0: IOM
x
– IN D00…IN D07
Group 1: IOM 1 – IN D10…IN D13 (for DI-810x)
IOM
x
– IN D10…IN D17 (for DI-610x, DI-811x)
For the power monitoring, the last input of a group (IN D07 and IN D13 resp. IN D17) must be
wired with the protected sensor voltage. Thereby the number of process information items is
reduced to 7 resp. 3 inputs for each group.
By means of a further parameter, the power monitoring can be parameterized this way, that
not one input for each group is responsible for the monitoring, but the last input of an
I/O module for the entire automation unit. Thereby the desired I/O module is selected.
Note
With a mixture of 1 ms and 10 ms input modules, the power monitoring should be set on an input module
with 1 ms accuracy.
You find further information in the manual
SICAM RTUs Common Functions Peripheral Ele-
ments According to IEC 60870-5-101/104, chapters "Single-Point Information" and "Double-
Point Information", respectively in the section "Sensor Voltage Monitoring (Power Monitoring)"
.
5.1.9.5.2 Counting Pulse Acquisition
Standard Counting Pulse Acquisition
For the acquisition of counting pulses, an appropriate digital input module must be equipped,
and the DI signals to be used must be configured.
Power Monitoring
You can activate the power monitoring for digital inputs jeweils with the parameter
SVM_monitoring
. The monitoring takes place by groups:
Group 0: IOM
x
– IN D00…IN D07
Group 1: IOM 1 – IN D10…IN D13 (for DI-810x)
IOM
x
– IN D10…IN D17 (for DI-610x, DI-811x)
For the power monitoring, the last input of a group (IN D07 and IN D13 resp. IN D17) must be
wired with the protected sensor voltage. Thereby the number of process information items is
reduced to 7 resp. 3 inputs for each group.
By means of a further parameter, the power monitoring can be parameterized this way, that
not one input for each group is responsible for the monitoring, but the last input of an
I/O module for the entire automation unit. Thereby the desired I/O module is selected.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...