Engineering via SICAM WEB
226
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Example: Digital input – double-point information, counter value
Update Counter Value
Counter values (TI 37) are not transmitted by the peripheral element upon each change, but
by means of a corresponding counter interrogation. With that, the displayed process value can
be also updated.
If a counter value is assigned on the selected DI module, then a button appears below the sta-
tus area.
•
In order to initiate the counter interrogation, click on the button
•
Select in the dialog the parameterized counter group (or all groups)
•
Select the desired action:
─
Example: “Freeze and transmit”, if you want to update the status display
─
Example: “Freeze with reset and transmit”, if you want to set the value to 0 and update
the status display
•
After that, click on the button
•
Click on the button
in order to close the dialog
The updated process value of the requested group is now displayed.
Note
The counter group and action correspond to the identifiers
FRZ
and
RQT
in the message to the peripheral
element.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...