Engineering via SICAM WEB
230
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
This is how to change a process value:
Example: double command output
•
In the directory tree, mark the corresponding DO module
•
Click on the side bar left beside the status area, if you want to extend it
•
Mark the row with the desired datapoint
Control area:
•
Select a “New value”
The data format corresponds to the setting of the data point on the I/O module (signal list).
•
Select the “Qualifier of command“ option
With selection
undefined
the settings of the respective data point on the I/O module (
out-
put_t_0
,
output_t_1
) are used for the duration for the command output.
With selection
Short command execution time
or
Long command execution time
the
corresponding values of the
AU common settings
are used for the duration for the
command output.
With selection
Persistant command
a continuous command is output (only with pro-
cessing type DO_SX and DO_DX).
•
Enter the “Originator“
This value defines the source address for the respective command (
0
…
255
).
•
Select the “Select before execute“ option
With selection
Yes
and button you activate the select command. You activate the ex-
ecute command, when you click on the button once more within the adjusted time
(
select_execute_t
).
With selection
No
and button you activate the execute command directly.
The new process value is transferred to the target device and displayed in the column
Value
.
You find further details in the manual
SICAM RTUs Common Functions Peripheral Elements
According to IEC 60870-5-101/104,
chapter
"Pulse Commands", section "Functions Inde-
pendent of the Hardware of the Systemelement", sections "Select and Execute Command",
"Set Control Location", "Command Output Time"
.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...