Connection
7.1 General connection drawings
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
67
For the circuit diagram illustrated here, the following parameters are to be set:
Terminal Parameter
code
Setting
P05.07
Breaker pulse or breaker continuous
15(INP1
)
P10.01.01 Line 1 breaker closed (feedback 1)
16(INP2
)
P10.02.01 Line 2 breaker closed (feedback 2)
17(INP3
)
P10.03.01 Line 1 circuit breaker protection (Trip 1)
18(INP4
)
P10.04.01 Line 2 circuit breaker protection (Trip 1)
25(OUT
4)
P11.04.01 Open Line 1 circuit breaker
27(OUT
5)
P11.05.01 Close Line 1 contactor/circuit breaker
28(OUT
6)
P11.06.01 Open Line 2 circuit breaker
30(OUT
7)
P11.07.01 Close Line 2 contactor/circuit breaker