Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
135
P08
Communi-
cation
COMn (n =
1/2)
Designation on
ATC display
Description
Unit
Default
Range
P08.n.06 IP address
IP address
– TCP-IP coordinates for applications with an
Ethernet
interface.
Note: Cannot be used with RS458 expansion
module.
192.168.1.
1
000.000.000.
000 –
255.255.255.
255
P08.n.07 Subnet mask
Subnet mask
- see Parameter 08.n.06
0.0.0.0
000.000.000.
000 –
255.255.255.
255
P08.n.08 TCP-IP port
TCP-IP port
- see Parameter 08.n.06
1001
0 - 32000
P08.n.10 Client / Server
Client / Server
– Enabling of the TCP-IP connection.
Server = Waiting for connection of
a remote client. Client = Establishes the con-
nection with a remote server.
Server
Client
Server
P08.n.11 Remote IP address Remote IP address
– Coordinates for the connection with the re-
mote server, if P08.n.10 is configured on client.
000.000.00
0.000
000.000.000.
000 –
255.255.255.
255
P08.n.12 Remote IP port
Remote IP port
- see Parameter 08.n.11
1001
0 - 32000
P08.n.13 IP gateway ad-
dress
IP gateway address
- see Parameter 08.n.11
000.000.00
0.000
000.000.000.
000 –
255.255.255.
255
Содержание SENTRON ATC6300