Operation
8.1 Operating modes of the ATC6300
3KC ATC6300 transfer control device
102
Manual, 03/2018, L1V30535632002A-01
8.1.2
OFF mode (OFF)
In this mode the device is disabled and performs no actions.
All displays, both of the measurements and status LEDs, remain active.
If the transfer control devices are pulse controlled, both Open and Close controllers remain
disabled in the OFF mode. In the case of continuous signal control, on the other hand, the
behavior can be selected by means of Parameter P05.10.
To call up programming menus, you must always switch to the OFF mode first. By pressing
the OFF/RESET key, retained alarms can be canceled, provided the causes of the alarms
have been eliminated.
8.1.3
Manual mode (MAN)
In manual mode the switching devices can be controlled manually. This enables the user to
switch freely between the power sources.
Procedure for manual switching via the operator panel
For the network/network application:
1.
Select the MAN operating mode.
On selection of the mode, the following window opens:
2.
Using the MAN key, select the source that you want to close.
3.
Press the
▲ and ▼ keys to open or to close the selected source.