Functions
5.1 Basic functions
3KC ATC6300 transfer control device
48
Manual, 03/2018, L1V30535632002A-01
5.1.6.2
Alarm description
The predefined alarms have the following properties:
Code Description
Cause of alarm
A01
Battery voltage too low The voltage of the DC supply is below the lower threshold limit for longer than the set
time.
A02
Battery voltage too high The voltage of the DC supply is above the upper threshold limit for longer than the set
time.
A03
Line 1 circuit breaker
timeout
The Line 1 switching device has not performed any opening or closing operation within
the set maximum period. Once the alarm has been triggered, the ON or OFF command
is inhibited. The alarms are only triggered if at least one of the two energy sources is
available, that is to say it is within the limits.
A04
Line 2 circuit breaker
timeout
The Line 2 switching device has not performed any opening or closing operation within
the set maximum period. Once the alarm has been triggered, the ON or OFF command
is inhibited. The alarms are only triggered if at least one of the two energy sources is
available, that is to say it is within the limits.
A05
Line 1 wrong phase
sequence
The phase sequence measured on Line 1 does not match the programmed phase
sequence.
A06
Line 2 wrong phase
sequence
The phase sequence measured on Line 2 does not match the programmed phase
sequence.
A07
Load not powered
timeout
Either because the power supplies were not available, or because both switching de-
vices have remained open, the load has been de-energized for longer than the time
programmed with P05.11.
A08
External battery charger
failure
This alarm is triggered by the input programmed for the charger alarm function if at
least one energy source is within the limits.
A09
Emergency
Alarm triggered by opening the external emergency input. Both switching devices are
opened (see Table of functions of the digital inputs (Page 108)).
A10
Line 1 breaker protec-
tion trip
The Line 1 breaker has opened because an overcurrent protection device has tripped.
This is signaled by activation of the input with function Line 1 breaker protection trip
(see Table of functions of the digital inputs (Page 108)).
A11
Line 2 breaker protec-
tion trip
The Line 2 breaker has opened because an overcurrent protection device has tripped.
This is signaled by activation of the input with function Line 2 breaker protection trip.
A12
Line 1 generator not
available
If the input with the function "Generator ready 1" is opened, this alarm is triggered (see
Table of functions of the digital inputs (Page 108)).
A13
Line 2 generator not
available
If the input with the function "Generator ready 2" is opened, this alarm is triggered (see
Table of functions of the digital inputs (Page 108)).
A14
Maintenance Hours 1
This alarm is triggered if the maintenance hours for Line 1 reach the value zero. See
Menu P12 - Miscellaneous (Page 139) Use this in order to reset operating hours and
alarm.
A15
Maintenance Hours 2
This alarm is triggered if the maintenance hours for Line 2 reach the value zero. See
Menu P12 - Miscellaneous (Page 139) Use this in order to reset operating hours and
alarm.
A16
Maintenance operations
1
This alarm is triggered if the number of operating cycles for Line 1 reaches the value
set in Menu P12. Use command menu to restore operation and reset the alarm.
A17
Maintenance operations
2
This alarm is triggered if the number of operating cycles for Line 2 reaches the value
set in Menu P12. Use command menu to restore operation and reset the alarm.
A18
Auxiliary voltage failure The device that manages the draw of auxiliary voltage supply from one of the available
lines signals a failure or improper operation.
UA1.
UA4
User alarm
The user alarm is generated by enabling the variable or associated input in Menu P15.