Technical specifications
3KC ATC6300 transfer control device
196
Manual, 03/2018, L1V30535632002A-01
Real-time clock
Energy storage
Stored-energy capacitors
Operating period without power supply
5 minutes
Digital inputs: Terminals 15-20
Input type
Negative
Input current
≤
8 mA
Input signal - logical state "0"
≤
2
Input signal - logical state "1"
≥
3.4
Input signal delay
≥
50 msec
Relay outputs OUT1 and OUT2: Terminals 9, 10 and 11, 12
Contact type
2x 1 NO contacts
Rated contact current
AC1 8 A 250 V
DC1 8 A 30 V
AC15 1.5 A 250 V
UL Rating
B300
30 V DC 1A pilot duty
Output voltage (maximum)
250 V AC
Mechanical / electrical endurance (cycle)
1x10^7 / 1x10^5
Design of insulation
Single between OUT1 and OUT2
Double for the remaining groups
Insulation voltage U
i
250 V AC
Single / double
Impulse withstand voltage U
imp
4.8 kV / 7.3 kV
Operating frequency impulse withstand volt-
age
1.5 kV / 3 kV
Relay output OUT3: Terminals 22, 23, 24
Contact type
1 CO contact
Rated contact current
AC1 8 A 250 V
DC1 8 A 30 V
AC15 1.5 A 250 V
UL Rating
B300
30 V DC 1A pilot duty
Output voltage (maximum)
250 V AC
Mechanical / electrical endurance (cycle)
1x10^7 / 1x10^5
Insulation voltage U
i
250 V AC
Impulse withstand voltage U
imp
7.3 kV
Operating frequency impulse withstand volt-
age
3 kV
Содержание SENTRON ATC6300
Страница 1: ...Manual 3KC ATC6300 Transfer Control Device Monitoring Devices 03 2018 Edition SENTRON siemens com 3KC ...
Страница 2: ......
Страница 14: ......
Страница 20: ......
Страница 64: ......
Страница 116: ......
Страница 146: ......
Страница 176: ......
Страница 204: ......
Страница 210: ......