MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
165
③
Key press simulation
The following values must be sent to the address 2F0AH in order to simulate the
corresponding key press:
Value
Function
0x8001
Key ↑
0x8004
Key →
0x8200
K
ey ↓
0x8400
Key ✓
0x8800
Key ←
0x0002
MAN mode
0x0020
OFF mode
0x0040
AUT mode
Execution of the command menu
④
The following values between 0 and 15 must be sent to the address 2F0AH in order to
execute the corresponding command:
Value Function
0
Reset maintenance 1
1
Reset maintenance 2
2
Reset maintenance operations 1
3
Reset maintenance operations 2
4
Reset general counters CNTx
5
Reset LIMx limits
6
Reset hours counter Line 1 / Line 2
7
Reset hour counters Breaker 1 / Breaker 2
8
Reset breaker operation
9
Reset event log
10
Reset default parameters
11
Save parameters in backup memory
12
Reload parameters from backup memory
13
Forced changeover I / O
14
Reset A03 - A04 alarms
15
Simulates line failure