4. Expand the displayed information for the "Home or Work" network profile.
5. Select the following check boxes:
– Disable "File and printer sharing"
– Disable "Client for Microsoft network"
– Enable the ISO protocol
Note
Special features of communication using a server with several network adapters
Read the information on this in the following documentation:
● Configuration manual
Process Control System PCS 7; Engineering System
● Configuration manual
Process Control System PCS 7; Operator Station
●
WinCC Information System:
Check the access point for each PC station
Perform the following steps on all PC stations:
1. In the tree view, select the "Access Points" folder.
2. In the list, select "S7ONLINE".
3. Select Properties in the shortcut menu.
The "S7ONLINE properties" dialog box opens.
4. Check the entry in the "Assigned interface parameter assignment" box. "PC internal (local)"
must be set. Change the settings, if necessary.
5. Click "OK".
Additional information
You can find information about suitable standard network adapters and (CP 16xx)
communications processors in the product overview
Process Control System PCS 7; Released
Modules.
5.7.8
How to make settings for standard network adapters
Procedure
If you want to use the TCP/IP protocol on the plant bus, you will need to perform the following
tasks for all standard network adapters on the plant bus:
1. Open the dialog for setting the Network Connections.
2. Select the plant bus in the "Network Connections" dialog box.
3. Select the menu command File > Properties.
Installing PC stations
5.7 Preparing PC stations
PCS 7 - PC Configuration (V8.2)
Installation Manual, 03/2016, A5E36200050-AB
111
Содержание PCS 7
Страница 6: ...Index 151 Table of contents PCS 7 PC Configuration V8 2 6 Installation Manual 03 2016 A5E36200050 AB ...
Страница 8: ...Security information PCS 7 PC Configuration V8 2 8 Installation Manual 03 2016 A5E36200050 AB ...
Страница 12: ...Preface PCS 7 PC Configuration V8 2 12 Installation Manual 03 2016 A5E36200050 AB ...
Страница 156: ...Index PCS 7 PC Configuration V8 2 156 Installation Manual 03 2016 A5E36200050 AB ...