ECO REFERENCE MANUAL
17-2
S elec t D isplay via
P aram eter 001
in the E xpert
P aram eter M ode
D ispla y frequency
P aram eter 001
0 = O utput frequency
D ispla y m otor current
P aram eter 001
2 = M otor current
D ispla y m otor speed
P aram eter 001
5 = M otor speed (R P M )
Display Parameters
R am p-up tim e
P aram eter 002
0 -150 sec
R am p-dow n tim e
P aram eter 003
0 -150 sec
D igit. freq. setpoint
P aram eter 006
0 = m anual setpoint
1 = analog/2 = digital se tup
Hand/A uto
P aram eter 007
0 = Hand
1 = A uto
M inim um m otor freq.
P aram eter 012
0 - 150 Hz
M axim um m otor freq.
P aram eter 013
0 - 150 Hz
S tart on the Fly
P aram eter 016
0 = disable 2 = enable
Nom inal rating plate
frequency for m otor
P aram eter 81
0 - 150 Hz
Nom inal rating plate
speed for m otor
P aram eter 82
0-9999 U/m in
Nom inal rating plate
current for m otor
P aram eter 83
0,1 - 300A
Nom inal rating plate
voltage for m otor
P aram eter 84
0 - 1000V
Nom inal rating plate
pow er for m otor
P aram eter 85
0,12 - 250 kW
E nable E xpert para.
P aram eter 199
B asic param eter 0
E xpert param eter 1
Basic Parameters
A utom atic resta rt
after m ains failure
P aram eter 015
0 = display/1 = enable
A utom atic resta rt after
fault
P aram eter 018
0 = disable/1 = enable
A nalogue input
P aram eter 023
0 = 0-10V /0-20m A
1 = 2-10V /4-20m A
S kip frequency
P ara 027/028/0 29
0 - 150 Hz
Input term inal function
P aram eter 051-056
see table
S election relay o utput
P aram eter 061/062
see table
D C injection bra king
P aram eter 073
0 - 200%
P ulse frequency
P aram eter 076
see table
M otor current lim it
P aram eter 086
0 - 200%
S ee R eference
M anual for m ore
E xpert P aram eters
Expert Parameters
Commisioning
M ICRO M AST ER Eco