ECO REFERENCE MANUAL
13-8
Analogue input 1 type
0 - 2
[0]
Sets analogue input type for analogue input
1, in conjunction with the settings of the DIP
selector switches 1, 2 and 3 (See
see the
DIP Selector Switches figure in this section)
0 = 0 V to 10 V/ 0 to 20 mA Unipolar input
1 = 2 V to 10 V/ 4 to 20 mA Unipolar input
2 = 2 V to 10 V/ 4 to 20 mA Unipolar input
with controlled start/stop when using
analogue input control.
Analogue output 1
Models above 7.5kW only
0 - 105
[0]
This provides a method of scaling the
analogue output 1 in accordance with the
following table:
Use range 0 - 5 if minimum output value = 0
mA.
Use range 100 - 105 if minimum output
value = 4 mA
P025= Selection Analogue Output
Range
Limits
0/4 mA
0/100 Output frequency 0 Hz
1/101 Frequency setpoint 0 Hz
2/102 Motor current 0A
3/103 DC-link voltage 0 V
4/104 Motor torque -250%
5/105 Motor RPM 0
•
Analogue output 2 (MDV
only)
0 - 105
[2]
This provides a method of scaling the
analogue output 2 in accordance with the
table shown in P025.
•
Skip frequency 2 (Hz)
0 - 150.0
[0.0]
See P014.
•
Skip frequency 3 (Hz)
0 - 150.0
[0.0]
See P014.
•
Skip frequency 4 (Hz)
0 - 150.0
[0]
See P014.
•
Fixed frequency1 (Hz)
0 -
150.00
[5.00]
Valid if P006 = 2 and P055 = 6 or 18
•
Fixed frequency 2 (Hz)
0 -
150.00
[10.00]
Valid if P006 = 2 and P054 = 6 or 18
•
Fixed frequency 3 (Hz)
0 -
150.00
[15.00]
Valid if P006 = 2 and P053 = 6 or 18