ECO REFERENCE MANUAL
13-5
Parameter
Function
Range
Default
Units
Keypad control
0 or 1
1
-
The value of this parameter (0 or 1) configures keypad control.
0 =
Control is by digital inputs (P051 to P055 or P356 - refer to Expert mode)
1 =
Front panel (keypad) control enabled. However, the level of control enabled from the keypad is
determined by the values of P121 and P124 (refer to Expert mode).
Minimum motor frequency
0.0 - 150.0
0.00
Hz
This value sets the minimum motor frequency and must logically be less then the value of P013 (see
below
Minimum motor frequency
0.0 - 150.0
50.00
60.0 (North America)
Hz
This value sets the maximum motor frequency. To maintain stable operation, this value should not
generally exceed the nominal rating plate motor nominal frequency when operating pumps and fans.
Start on the fly
0 or 2
0
Flying restart
P016=0 Flying restart disabled
P016=2 Flying restart enabled
Allows the inverted to start onto a spinning motor.
Always enter the correct motor nameplate details when enabling this feature.
Motor rating plate nominal
frequency
0 - 150.0
50.00
60.0 (North America)
Hz
Motor rating plate nominal speed
0 - 999
Depends on inveter
rating
RPM
Motor rating plate nominal
current
0.1 - 300.0
Depends on inveter
rating
A
Motor rating plate nominal
voltage
0 - 1000
Depends on inverter
rating
V
Motor rating plate nominal power
0.12 - 250.00
Depends on inverter
rating
kW (hp
- North
America)
* Parameters P081 to P085 - Notes
-
These parameters must be set for the particular motor being controlled by the inverter. You must
use the data provided on the motor’s rating plate.
-
Perform an automatic calibration (P088 = 1 - refer to Expert mode) if any of the parameters P081 to
P085 are changed from their factory default settings.
-
When the inverter is set-up for North America operation (P101 = 1 - refer to Expert mode), P081 will
default to 60 Hz and P085 will indicate in hp (range = 016 to 250).