ECO REFERENCE MANUAL
13-20
Transducer type
0 - 1
[0]
0 = An increase in motor speed causes an
increase in transducer voltage/current
output.
1 = A increase in motor speed causes an
decrease in transducer voltage/current
output.
Transducer reading (%)
(unscaled)
0.00-
100.00
[-]
Read-only. Value is a percentage of full
scale of the selected signal input
(i.e. 10 V or 20 mA).
•
0% setpoint
0.0 -
100.00
[0.0]
Value of P210 to be maintained for 0%
setpoint.
•
100% setpoint
0.0 -
100.00
[100.00]
Value of P210 to be maintained for 100%
setpoint.
PID frequency cut-off.
0 - 1
[0]
0 = Normal operation.
1 = Switch off inverter output at or below
minimum frequency.
For correct operation of P220 ensure that
P202 >0.
•
Minimum analogue
frequency for analogue
setpoint 2 (Hz)
0 - 150.0
[0.0]
Frequency corresponding to the lowest
analogue input value, i.e.
0 V/0 mA or 2 V/4 mA, determined by P323
and the settings of the DIP selector switches
4 and 5 (
see the DIP Selector Switches
figure in this section)
. This can be set to a
higher value than P322 to give an inverse
relationship between analogue input and
frequency output
(see diagram in P322)
.
•
Maximum analogue frequency for
analogue setpoint 2 (Hz)
0 - 150.0
[50.0]
(60) North
America
Frequency corresponding to the highest analogue
input value, i.e.
10 V or 20 mA, determined by P323 and the setting of
the DIP selector switches 4 and 5 (
see the DIP
Selector Switches figure in this section)
. This can be
set to a lower value than P321 to give an inverse
relationship between analogue input and frequency
output. i.e.
V/ I
P322
P322
P321
P321