ECO REFERENCE MANUAL
13-22
State of digital inputs
0 - 3F
[-]
Read-only. Provides a HEX representation
of a 6-digit binary number of which the LSB
= DIN1 and the MSB = DIN6 (1 = ON, 0 =
OFF).
e.g. If P723 = B, this represents ‘001011’ -
DIN1, DIN2 and DIN4 = ON, DIN3 , DIN5
and DIN6 = OFF.
•
Relay output control
0 - 3
[0]
Enables control of the output relays. Used in
conjunction with P720, e.g. setting P724 = 1
(relay 1 = ON) has no effect unless P720 =
1, 3, 5,or 7.
0 = Both relays OFF / de-energised
1 = Relay 1 ON / energised
2 = Relay 2 ON / energised
3 = Both relays ON / energised
Analogue input 2 voltage
(V)
0.0-10.0
[-]
Read only. Displays the analogue input 2
voltage (approximate) only when analogue
input 2 is active (P051 to P055 or P356 = 24
and the respective digital input is high).
Analogue output 2 current
(mA) Models above 7.5kW
only
0.0-20.0
[0.0]
Allows direct control of the analogue output
2 current if P720 = 4, 5, 6 or 7.
•
Local/USS mode
0 - 4
[0]
Sets the inverter for local control or USS
control over the serial link:
0 = Local control
1 = Remote control (and setting of
parameter values)
2 = Local control (but USS control of
frequency)
3 = USS control (but local control of
frequency)
4 = Local control (but USS read and write
access to parameters and facility to
reset trips)
When operating the inverter via remote
control (P910 = 1 or 2 ), the analogue input
remains active when P006 = 1 and is added
to the setpoint.
Software version
0.00 -
99.99
[-]
Contains the software version number and
cannot be changed.
•
Equipment system number
0 - 255
[0]
You can use this parameter to allocate a
unique reference number to the inverter. It
has no operational effect.