ECO REFERENCE MANUAL
13-17
•
Operation for Europe or
North America
Factory Default
0 for 230V Eco
2 for 380V to 500V Eco
2 for 525V to 575V Eco
0 - 2
[0 or 2]
This sets the inverter for European or North
America supply and nominal rating plate
frequency for the motor to:
0 = Europe (50 Hz and power ratings to kW)
1 = North America NEMA (60 Hz and
power ratings to hp)
2 = Automatic Selection based on mains
voltage
mains voltage <450V goes to 0
mains voltage >450V goes to 1
After setting P101 =0 or 1 the inverter must
be re-set to factory defaults, i.e. P944 = 1 to
automatically set P013 = 60Hz, P081 =
60Hz, P082 = 1680rpm and P085 will be
displayed in hp.
After setting P101 =2 the inverter will
automatically re-set to factory defaults, i.e.
P944 = 1
Inverter power rating
(kW/hp)
1.1 - 90.0
[
¶¶¶
]
Read-only parameter that indicates the
variable torque power rating of the inverter
in kW. E.g. 7.5=7.5kW
If P101 = 1 then the rating is displayed in hp.
Inverter type
1 - 10
[
¶¶¶
]
Read-only parameter.
1 = MICROMASTER 2nd Generation
(MM2)
2 = COMBI MASTER
3 = MIDIMASTER
4 = MICROMASTER Junior (MMJ)
5 = MICROMASTER 3rd Generation (MM3)
6 = MICROMASTER Vector (MMV)
7 = MIDIMASTER Vector (MDV)
8 = COMBIMASTER 2nd Generation
9 = MICROMASTER Eco
10 = MIDIMASTER Eco