E3X102/103 Master module (supersedes E3X101)
54
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
LED ”Battery fault
–
Battery voltage < 23 V
–
Open line to battery or fuse F501 / F502 blown
–
Autom. test to indicate battery presence negative
–
Autom. battery load test negative
LED ”Power supply fault
–
Input voltage > 31.0 V –> power unit malfunction
–
EEPROM check sum error
LED ”Power on”
–
Input voltage > 28.5 V
c) Operation with
external voltage (in-
stead of battery)
LED ”Battery fault
–
Battery voltage or external voltage < 23 V or > 31.0 V
–
Autom. presence test (external voltage) negative or fuse F501 / F502
blown
LED ”Power supply fault
–
Input voltage > 31.0 V –> power unit malfunction
–
EEPROM check sum error
LED ”Power on”
–
Input voltage > 28.5 V
d) Operation without
battery or external
voltage
LED ”Battery fault
–
no function
18 Programming switch "S3": Choice of "I-Bus address battery charger"
To set I-Bus address for the
Function unit ”Charge /monitor battery”
. This unit is
an I-Bus user (as e.g. line module) and must have an individual address (number).
This is set on programming switch ”S3”.
Maximum 16 I-Bus devices
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off
off
2
2 off
on
off off off
off
3
3
on
on
off off off
off
4
4 off
off
on
off off
off
5
5
on
off
on
off off
off
6
6 off
on
on
off off
off
7
7
on
on
on
off off
off
8
8 off
off
off
on
off off
9
9
on
off off
on
off off
10
10 off
on
off
on
off off
11
11
on
on
off
on
off off
12
12 off
off
on
on
off off
13
13
on
off
on
on
off off
14
14 off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” are set to ”off” at the factory