E3C010 Battery charging module (superseded by E3C011)
60
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
11.4 Important
components
ASIC
I-Bus
ON
ON
S1
K1
ST1
S2
S3
F503
F502
F501
1
4
µ
P
1
1
1
2
3
4
5
6
7
Legend:
1 Fuses
F501
6,3 A/T*
Battery "Positive"
F502
6,3 A/T*
Battery "Negative"
F503
6,3 A/T*
Battery "Center"
* Fuse with high breaking capacity (sand-filled)
2
Programming switch "S3": Set "I-Bus address"
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus users.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off
off
2
2 off
on
off off off
off
3
3
on
on
off off off
off
4
4 off
off
on
off off
off
5
5
on
off
on
off off
off
6
6 off
on
on
off off
off
7
7
on
on
on
off off
off
8
8 off
off
off
on
off off
9
9
on
off off
on
off off
10
10 off
on
off
on
off off
11
11
on
on
off
on
off off
12
12 off
off
on
on
off off
13
13
on
off
on
on
off off
14
14 off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” are set to ”off” at the factory