E3M110 Line module ”AnalogPLUS” (superseded by E3M111)
99
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
23.4 Important
components
1
2
3
4
5
6
ST1
F1
F16
F17
F18
K1
S3
ASIC
I-BUS
1
1
4
ON
µ
P
H1
Legend:
1
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory
2
Flachband-Header "ST1" (26-polig): I-Bus
3
Fuses:
F17 1 A/T* Module supply 24 V
F18 1 A/T* Module supply 5 V
* Fuse with high breaking capacity (sand-filled)
4
Plug-in terminals "K1": Supply to "I-Bus" modules
5
Maintenance LED "H1":
pulsating = Communication with detection line(s) ok
continuous = Module probably defective
not active = no line connected, or not programmed