E3I040 I-Bus/LON module
116
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
28.5 Important
components
7
6
5
4
3
2
1
8
9
ASIC
S3
F1
ST1
H3
R60
X30
H1
H2
K1
1
4
1
ON
RAM
EPROM
S1
µ
P
LON
C
µ
Legend:
1
Jumper "X30": Ground fault monitoring 'LON-Bus'
'out'
=
inactive (factory setting)
'in' =
active
(Details application –> see chapter 6)
2
LED "H3":
inactive
–> normal operation
lit or flashing –> EPROM is missing or faulty
3
Service key "S1": no function
4
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory
5
Flat cable header "ST1" (26-pin): I-Bus