B3Q4.. / 560 Control terminal AlgoPilot
173
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
12 Jumpers "X/Y31…X/Y34": Programming of terminals "K7"
Use of AlgoPilot B3Q...
0
Ω
resistors
”CT” + Supply from control unit (Input)
X31 + X32 + X33 + X34
”CT” + autonomous supply (Output)
Y31 + Y32 + Y33 + Y34
”CI” + autonomous supply (Output)
Y31 + Y32 + Y33 + Y34
13 Fuses 'F1', 'F2' 0.8 A/T: Supply input / supply output with high breaking ca-
pacity (sand-filled)
14 Plug-in terminals 'K7': (orange 6-pin): "24 V supply voltage" (18...45 VDC)
15 Fuses 'F3', 'F4' 0.5 A/T: Input/output emergency operation circuit (Fuses with
high breaking capacity, sand-filled)
16 Plug-in terminals 'K6' (orange 5-pin): "Emergency operation circuit"
17 Connector 'ST6': Hall switch to monitor the Plexiglas door (option)
18 Resistors to modify the C-Bus impedance:
Position
Impedance value 110
Ω
,
e.g. for G51 0.6Ø
Impedance value
50
Ω,
e.g. for MICC
R49 / 50
402
Ω
182
Ω
R31 / 32 / 33 / 34
110
Ω
49,9
Ω
Impedance adaptation only required if C-Bus line is > 100 m. For other impedance
values than 110
Ω
or 50
Ω
consult document e1594.
19 Plug-in terminals 'K5' (grey 4-pin): "C-Bus"
20 Switch 'S5': "Service functions" S1-1...4 must be set to OFF
S5-1
on
Maintenance mode: Blocks all control outputs
S5-3
S5-2
off
on
Event memory, normal mode
Event memory, freeze current contents
S5-4
unused
21 Plug-in terminals 'K4' (orange 2-pin): "External operation enabling"
22 Connector 'ST5': unused (tamper contact)
23 Jumper 'X30': Ground fault monitoring 'C-Bus'
J1 =
not
monitored
J2 =
monitored
'removed' = the other monitors (factory setting)
Î
for application details –> see chapter 6
24 Connector 'ST4': Parallel indicator panel B3R051, Mimic display board
K3R071/72
25 Connector 'V2': Foil-covered keys (front terminal)
26 Programming for RAM/EPROM:
RAM/EPROM:
RAM
256Kx8Bit or
512Kx8Bit
EPROM
512Kx8Bit
EPROM
1024Kx8Bit
0
Ω
resistors
X1
X2 / X3 / X4 / Y5
X2 / X3 / X4 / X5
27 Connector 'ST3': Illumination for LCD