E3G060 Control module ”monitored” (Part No 542539)
145
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
3
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
Nr.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory
4
Flachband-Header "ST1" (26-polig): I-Bus
5 0
Ω
resistor: no function (factory setting X11)
6
Maintenance switch "S2": To switch on maintenance LEDs for test purposes.
In addition to the control line, it also enables the activation of the correspond-
ing LED (H1...H6).
S2-on
= LED (H1..H6) lights if the control line is activated.
7
Plug-in terminals "K2": to synchronize Horns or external oscillator input
8
Plug-in terminals "K1": Supply for "I-Bus" modules
9
Plug-in terminals "K3": External horn supply
10 Fuse: 'F19' 6.3 A/T for internal module and horn if internal supply (K1)
11 0
Ω
resistor: Supply for 6 horn outputs (X1-2..14)
X12 = internal supply (factory setting) (K1)
Y12 = external supply (K3)
12 Fuses: 'F1, F3, F5, F7, F9, F11' 2 A/T Control lines monitored (Fuses with
high breaking capacity, sand-filled)
13 Test LEDs 'H1...H6' at rear allocation of the individual LEDs H1...H6 –> see