E3M080 Line module ”Collective”
95
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
22.5 Compatibility
(detector <–> line type)
Incompatible
–
AT3
–
ATAN3
–
MS6 detectors
–
External response indicators with incandescent lamps
–
SE20 with incandescent lamp as response indicator
–
FES 7.5 detectors
–
220 V detectors
Line type 11
Compatible
Î
Line termination with Transzorb 20 V
AlgoRex detectors:
DO110x , DT110x , DM110x, DC1192
Standard application, also for Ex detectors via
DC1192
Older detectors:
MS716 , MS9 , MLK20 , T2416/18 , D2417 , SE22, AT4x, AT5x without SE2
Base: Z74*, Z74A*, Z90, Z94, Z96
* Limitations:
Z74 and Z74A only from the 1988 model (year index W)
D900 only from the 1983 model (year index R)
–> if in doubt use line type 1
Ex detectors (without restrictions)
used via DC1192 with SB3: DO110x Ex, DT110x Ex
F911, D901, D921 with base Z91C/Z94C
D2401
Ex,
S2406Ex
F6A
Ex,
D6A
Ex
Line type 1
Compatible
Î
Line termination with EOL22(Ex)
AlgoRex detectors:
DLO1191, (with mixed lines also DO110x, DT110x, DM110x, DC1192)
for older detectors, also for mixed lines (newer
and older detector types)
Older detectors:
MS6* , MS7*, MS9 , MS24 , SE20* , SE22 , MLK20, AT4x, AT5x, SE2
Base electronics: Z70, Z72, Z72A, Z74, Z74A, Z90, Z94, Z96
Note:
–
replaces line type 2
Limitations: For MS6 and MS7 note the listed detector types and applications as stated
under 'Incompatibility'
Î
Not permissible with line type 2: DO110x, DLO1191
Line type 3 (Ex)
For Explosion hazard area with limitations:
–
Only with safety barrier SB2
Î
Via safety barrier SB2 and line termination
EOL22 (Ex)
–
Only without short to earth monitoring
For Ex detectors with limitations
–
Only 1 Ex-line per installation
or
Note:
–
replaces line type 13
–
several Ex lines, however with a common ground connection off all SB2s to the con-
trol unit, whereby the ground conductor must have a min. cross-sectional area of
1.5 mm
2
and be no longer then 50 m
Î
Comply with the local safety regulations
Compatible
DO110x Ex, DT110x Ex
F911, D901, D921 with base Z91C, Z94C
D2401 Ex, S2406 Ex
F6A Ex , D6A Ex
Î
Not permissible with line type 13: DO110x Ex