E3M120 Line module ”CBA8000/TS9000”
105
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
25.4 Important
components
1
2
3
4
5
6
7
S2
X1
[ST1]
LD1
ST1
[J1]
µ
P
K1
1
4
1
4
J6
1
ON
S1
LD2
LD3
LD4
LD5
EPROM
Legend:
1
Jumper "X1" [ST1]: 'in' = Watchdog active (factory setting)
'out' = for development only
2
Key "S2": Reset line interface
µ
P (not I-Bus controller)
3
Flat cable header "ST1" [J1] (26-pin): I-Bus
4
LED green "LD1": indicates power ON
5
Plug-in terminals "K1" [J6]: Supply to "I-Bus" modules
6
Programming switch "S1": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S1".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S1
No.
S1-1 S1-2 S1-3 S1-4 S1-5
S1-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S1-1...6" are set to "off" at the factory
7
LED red "LD2...LD5":
pulsating
= Communication between I-Bus and E3M120 ok
continuous
= Line reset or line pulled down to 0 V (short circuit)