E3L030 Control module VdS (VdS module)
135
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
32.6 Connections
Connect to
chassis ground
Connect to
chassis ground
max. 320mA
max. 50mA
max. 50mA
max. 50mA
max. 50mA
max. 50mA
max. 50mA
max. 50mA
max. 1A
max. 5
Ω
/ wire
Actuated or fault
Actuate
E3L030
1
2
3
4
5
6
7
8
9
10
11
12
+
-
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
+
-
+
-
+
Terminal block
X1
11
12
13
14
15
16
A
B
17
18
19
20
+
+24V
F2
F1
F3
F4
F5
F11
1
Module chassis ground
F12
F13
F14
F15
F16
Terminal block
X2
F17
F18
F19
F23
F24
-
F30
F27
F28
1
2
3
4
+
+
1
Plug-in terminals
K1
5V
Supply for
I-Bus modules
Double flat cable header
ST1
Data communication
I-Bus modules
Common
Indicator ÜE activated
Exting. system released
Spare
F6
F7
Reset fire alarm contr. unit
F8
Disable ÜE
F9
Aud. sign. disabled (key 5)
F10
Fire controls disabled (LED)
Check ÜE
unused
+24V
Actuate
Actuated
Common
F20
F21
F22
F25
F26
Monitoring (sabotage)
Activate unlocking
Acknowledgem. unlocking
Common
Door contact
Module chassis ground
Door switch
24V
F31
Remote transmission fire
unused
Door contact in
control unit
FBF
I2
I6
I4
I5
ÜE
2k2
FSD
3rd party
extinguishing
control unit
X15-6
X15-7
3k3
680
Ω
E3X...
(only if several E3X...
are used)
to other I-Bus modules
blue
blue
green
red
from previous I-Bus modules
to other I-Bus modules
from previous I-Bus modules
Fuses F1, F2 monitored
*
Peripheral equip-
ment outside the
control unit housing
3) Depending on the re-
quired length of line,
possibly run several
wires in parallel
F29
2)
If the control unit door is
open, the contact must
close
SST
GND
-
-
R
191
R
191
+
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED T5
LED 1
max. 50mA
Audible signals disabled
Audible signals disabled
Reset fire alarm contr. unit
Disable ÜE
Fire controls disabled
1) applies for control zones with the attribute ’FIRE control zone switching off’
-
-
max. 20
Ω
/ wire
FBF
1)
max. 10
Ω
/ wire
3)
3)
3)
max. 50
Ω
/ wire
max. 5
Ω
/ wire
3)
*
2)
max. 50
Ω
/ wire
ÜE
FSD
SST
26
P
in
26 Pin
680
Ω
*