AVL-1 Audio VoiceLink 

Operation and Installation 

Manual 

 

 
 
 
 
 
 
 
 
 

 

One Firelite Place 

Northford, CT  06472-1653 

        Telephone: 203-484-7161 

Fax: 203-484-7118 

 
 
 
 
Document 50120 Revision HManual Assembly) 
Part 

Number 

P82867 

Revision 

                Assembly 

Number 

A82633-002 

Revision 

E

 

www.PDF-Zoo.com

firealarmresources.com

Содержание AVL-1

Страница 1: ...lation Manual One Firelite Place Northford CT 06472 1653 Telephone 203 484 7161 Fax 203 484 7118 Document 50120 Revision HManual Assembly Part Number P82867 Revision H Assembly Number A82633 002 Revision E www PDF Zoo com firealarmresources com ...

Страница 2: ...us situation which if not avoided could result in minor or moderate injury It may also be used to alert against unsafe practices WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED COULD RESULT IN PROPERTY DAMAGE AND SERIOUS PERSONAL INJURY OR DEATH P82867 AVL 1 Manual Rev H August 2000 www PDF Zoo com firealarmresources com ...

Страница 3: ...IGNMENTS REVIEWED AND APPROVED BY QUALIFIED LEGAL AND SAFETY ADVISORS QUALIFIED REPRESENTATIVE S OF OWNER S AND USER S AND AUTHORITIES HAVING JURISDICTION CAUTION The AVL 1 printed circuit boards are sensitive to static electricity and have delicate components mounted on them Before handling either a board or any component on a board discharge any static electricity from your body by touching a gr...

Страница 4: ...tion Each manufacturer s fire alarm control panel audio system and notification appliance operates differently and has different features Before specifying installing operating testing maintaining or servicing a system carefully read the installation operation and testing manual for each piece of equipment and applicable codes Request that the local authority having jurisdiction inspect the propos...

Страница 5: ...ement In the event you cannot contact the installer contact the manufacturer WARNING THERE ARE CERTAIN HARDWARE FUNCTIONS ON THE AVL 1 WHICH ARE NOT SUPERVISED IF ANY SUCH HARDWARE FUNCTIONS FAIL THE AVL 1 MAY NOT PROVIDE THE INTENDED WARNING AND OR NOT INDICATE A TROUBLE CONDITION THE FOLLOWING HARDWARE FAILURES WOULD PREVENT THE AVL 1 FROM PROVIDING THE INTENDED WARNING 1 THE SHORT CIRCUIT DETEC...

Страница 6: ...ntrol 16 Recording a Voice File 17 Creating a String File 17 Transferring Data 18 Installati 21 Wiring Guidelines 22 Mounting 22 Field Wiring 24 Field Wiring Checkout 29 System Checkout 30 Ground Fault Detection Sensitivity Adjustment 30 Troubleshooting 31 Procedures A B C 32 Procedures D E 33 Procedure F G 34 Procedure H I J 35 Periodic Testing 36 Technical Specifications 37 Glossary 40 Limited W...

Страница 7: ...igure 3 AVL 1 Mounting 23 Figure 4 File Input Wiring 25 Figure 5 Audio Output Music Input Channel Playing Wiring 26 Figure 6 Input Voltage and Status Contact Wiring 26 Figure 7 Typical System Block Diagram 27 Figure 8 AVL 1 Main Board Layout 28 Figure 9 RS 232 Port Pin Out 29 Figure 10 RS 485 Port Pin Out 29 www PDF Zoo com firealarmresources com ...

Страница 8: ... internal operations with trouble diagnosis and notification Serial communication supervision and optional verification of serial commands with a trouble indication if an error is detected An optional telephone interface An RS 232 interface and an optional RS 485 A AVL 1 MUST BE PROPERLY INSTALLED PROGRAMMED AND CONNECTED TO A COMPATIBLE CONTROL PANEL AND AUDIO SYSTEM AND A POWER SUPPLY TO FUNCTIO...

Страница 9: ...AVL 1 Manual Rev H August 2000 Sheet 10 of 41 Figure 1 Basic Capabilities Of The AVL 1 Products www PDF Zoo com firealarmresources com ...

Страница 10: ...OPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS Input and Output Options Each AVL 1 model includes 8 inputs that can be used to activate file numbers 1 through 8 with a contact closure or a transistor switch across the corresponding input terminals The optional digital voice expansion modules DV EM can provide 32 inputs When a DV EM module is used the 8 inputs in the AVL 1 unit cann...

Страница 11: ... on the into file number 100 First into file number 101 Second into file number 102 Third into file number 103 Floor into file number 104 Create three string files as indicated File 1 ADD 100 ADD 101 ADD 104 END File 2 ADD 100 ADD 102 ADD 104 END File 3 ADD 100 ADD 103 ADD 104 END When file number 1 is selected to play There is a fire on the first floor will be played When file number 2 is selecte...

Страница 12: ...on completion of any lower priority file Any file that is interrupted by a higher priority file before it has completed playing will remain on the channel queue until it is allowed to replay completely If two or more files of equal priority are activated the files will play sequentially as long as the files are activated Priority 4 and Priority 5 files may be acknowledged Files are acknowledged by...

Страница 13: ...ile played alternately with other equal priority files acknowledged or reset System Pause The ability to have a pause between messages is provided Having a pause between all playing messages prevents messages from running together and then being misunderstood The system pause may be any value from 1 to 999 seconds Supervision A trouble condition indicates that the supervision functions have detect...

Страница 14: ...e condition will clear automatically as soon as audio is detected or the low impedance load is no longer detected respectively When no messages are playing the circuitry is continuously supervised for functionality If a circuitry failed condition is detected a trouble condition is indicated CAUTION External audio wiring is NOT supervised by the AVL 1 Notifier strongly recommends that the control p...

Страница 15: ...access key and password should only be given to authorized and properly trained personnel who are responsible for the operation testing and maintenance of the AVL 1 Memory Retention Battery The AVL 1 contains a memory retention battery to power the PSRAM IC s during periods when input power has been disconnected from the AVL 1 The battery s only function is to prevent the message files stored in t...

Страница 16: ...back circuit contains one volume control for each of the four output channels The locations of the six volume controls on the AVL 1 are shown in Figure 2 Note that all volume controls can be accessed without removing the printed circuit board cover The two input volume controls determine the record level of messages from each of the two sources If the input volume controls are set too high the Ana...

Страница 17: ... silence is required as part of a message the silence should be the result of a pause command in a string file to prevent indication of a trouble condition 13 Select DIAGNOSTICS from the main menu 14 Select VIEW FILE DATA from the diagnostics menu 15 Enter file number 16 Check priority level Creating a String File The following instructions will enable the user to create a non telephone string fil...

Страница 18: ... The AVL 1 will indicate an output channel error whenever audio is not detected for 3 or more seconds while voice files are playing If silence is required as part of a message the silence should be the result of a pause command in the string file to prevent indication of a trouble condition 13 Select DIAGNOSTICS from the main menu 14 Select VIEW FILE DATA from the diagnostics menu 15 Enter file nu...

Страница 19: ...n ultraviolet UV light source All Files Download Procedure 1 Select TRANSFER FILE from the main menu on the source AVL 1 2 Select MESSAGE STRING from the next menu 3 Select ALL from the next menu The length of time required to download each file will vary depending on the number types and sizes of the files to be downloaded A good rule of thumb is that downloading will require 30 seconds for every...

Страница 20: ...AVL 1 Manual Rev H August 2000 Sheet 21 of 41 Figure 2 AVL 1 Interior View www PDF Zoo com firealarmresources com ...

Страница 21: ... drawing of the complete system wiring Keep a copy of the system wiring drawing with the AVL 1 manual as a permanent record of the system wiring See the Wiring Guidelines and the Field Wiring sections to help develop this drawing 2 Carefully unpack the AVL 1 and make sure each item described on the packing slip is present and undamaged 3 Mount the AVL 1 and optional DV EM modules in the desired lo...

Страница 22: ...ed in conduit and wiring boxes depending on the size of the conduit the volume of the boxes and the gauge of the wire used Make sure that wiring used for AVL 1 DV EM installation complies with the latest NEC requirements for power limited circuits See the Field Wiring section for recommended wire sizes and wire type to use for all AVL 1 input and output lines Mounting The AVL 1 shall be mounted in...

Страница 23: ...AVL 1 Manual Rev H August 2000 Sheet 24 of 41 Figure 3 AVL 1 Mounting www PDF Zoo com firealarmresources com ...

Страница 24: ...ine resistors must have a 1 8W minimum power rating and 5 maximum tolerance AVL 1 dry contact inputs meet the requirements for power limited fire protective signaling circuits as defined in the National Electrical Code Each input meets Class B Style B supervision requirements for initiating device circuits The gauge of the wire necessary for dry contact input wiring may vary for each dry contact i...

Страница 25: ...e plug to the previous DV EM J2 female socket Optionally the DV EMs can also be interconnected using the CAB EM cable assembly Do not substitute alternate cables or connect field wiring to the eight AVL 1 dry contact inputs when any DV EM modules are used as the AVL 1 may fail to operate properly RS 232 Port Wiring One RS 232 port is provided It is a ten wire interface The pin out of the RS 232 po...

Страница 26: ...AVL 1 Manual Rev H August 2000 Sheet 27 of 41 Figure 5 Audio Output Music Input Channel Playing Wiring Figure 6 Input Voltage And Status Contact Wiring www PDF Zoo com firealarmresources com ...

Страница 27: ...AVL 1 Manual Rev H August 2000 Sheet 28 of 41 AVL 1 Figure 7 Typical System Block Diagram www PDF Zoo com firealarmresources com ...

Страница 28: ...AVL 1 Manual Rev H August 2000 Sheet 29 of 41 Figure 8 AVL 1 Main Board Layout www PDF Zoo com firealarmresources com ...

Страница 29: ...gnaling system wiring CAUTION Do not connect input voltage to any equipment until the field wiring has been inspected and approved Verify that the field wiring is in full agreement with this manual and with the detailed wiring layout prepared for this installation Ensure that no unwanted voltages are present on circuit conductors and ground Test all ungrounded connectors for electrical isolation f...

Страница 30: ...VL 1 ground fault detection sensitivity can be adjusted between 40K and 500K Ohms Selecting a high sensitivity high resistance will have a fast response to ground fault conditions but may also cause a high number of false trouble conditions Selecting a low sensitivity low resistance will greatly reduce the susceptibility to false trouble conditions but will slow the response to ground fault condit...

Страница 31: ... 1 inoperative condition steady on or troubleshooting required condition coded blinking Use Table 2 to determine the trouble condition and the correct troubleshooting procedure to follow System Normal LED Green System Trouble LED Amber Trouble Indicator LED Amber What it Means Troubleshooting Procedure On Off Off Normal Off Off Off Power Loss A Off On Off AVL 1 Inoperative B Off On Steady On AVL 1...

Страница 32: ...e plays then the amber trouble indicator LED is broken If after the above procedure is completed the trouble condition persists the trouble condition is caused by failed circuitry on the AVL 1 There are no field correctable failed circuitry problems on the AVL 1 AVL 1 s with failed circuitry shall be replaced immediately following the Replacement Procedure set forth previously in this section Proc...

Страница 33: ...th failed circuitry shall be replaced immediately following the Replacement Procedure set forth previously in this section Procedure E If the green system normal LED is off the amber system trouble LED is on and the amber trouble indicator LED flashes 3 blink pattern an input error has occurred An input error may be caused by 1 Open field wiring 2 No end of line resistor on an input line 3 Inputs ...

Страница 34: ...rly inserted output channel IC s in sockets S21 S4 S22 S6 S23 and S9 Note that once an IC has been inserted into sockets S21 S22 and S23 the AVL 1 will always check for it and give a trouble condition if it doesn t see it If after the above procedure is completed the trouble condition persists the trouble condition is caused by failed circuitry on the AVL 1 There are no field correctable failed ci...

Страница 35: ... trouble error is indicated perform the following 1 Check connection of memory retention battery 2 Replace memory retention battery If after the above procedure is completed the trouble condition persists the trouble condition is caused by failed circuitry on the AVL 1 There are no field correctable failed circuitry problems on the AVL 1 AVL 1 s with failed circuitry shall be replaced immediately ...

Страница 36: ...AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS In addition to testing required by relevant fire codes regulations and laws several hardware functions should also be tested The hardware functions that should be tested are as follows 1 The short circuit detection circuitry for any one or all of the eight contact inputs 2 The serial port receiver 3 The play contact for each of the four output chann...

Страница 37: ...ature 0 to 49 C Storage Temperature 20 to 70 C Humidity 85 5 30 2 C Non condensing Playback Memory Type PSRAM Memory Time 2 to 16 Minutes Bandwidth 70 Hz to 4000 Hz Maximum Files 999 Signal to Noise Ratio 51 dB THD 1 KHz full scale 5 5 Power Limited Wiring All AVL 1 circuits are power limited Therefore to maintain power limited ratings circuits connected to power supply auxiliary music input and r...

Страница 38: ...ast Messages Playing In One Channel 425mA 305mA 296mA Charge Messages Playing In Two Channels 460mA 320mA 310mA Mode Messages Playing In Three Channels 497mA 336mA 324mA Messages Playing In Four Channels 535mA 352mA 339mA Inrush Current Voltage 11VDC 24VDC 29VDC Current 12A 27A 35A The inrush current draw settles to a steady state current draw in 6 to 8 milliseconds Fuse F1 Telephone 500 mA 5 x 20...

Страница 39: ...normally energized Contacts transfer during trouble Rated 0 5 Amps at 30 VDC max resistive load WARNING DO NOT EXCEED THE RATINGS OF THE STATUS CONTACT EXCEEDING THE RATINGS MAY CAUSE THE RELAY TO FAIL IF THE RELAY FAILS THE AVL 1 MAY NOT BE ABLE TO INDICATE A TROUBLE CONDITION Channel Playing One for each channel Normally open contacts closed when channel is Contact playing Rated 0 5 Amps at 30VD...

Страница 40: ...erial port Some files are never intended to become message files they merely contain words or phrases that can be strung together to create new files that will become message files The new files will be assigned channel and priority designations that supersede previous channel and priority designations for the individual files in the new string M message An audio output generated and played throug...

Страница 41: ...TIONS BEYOND MANUFACTURER S CONTROL SOME OF THE MANUFACTURER S PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS THE MANUFACTURER DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIREMENTS THE MANUFACTURER SHALL...

Страница 42: ...1 Figure A 14 Data Field Format A 12 Figure A 15 Field Formats A 12 Figure A 16 File Information Field ASCII Legend A 13 Figure A 17 System Configuration Query Data Flow Diagram A 15 Figure A 18 System Configuration Query Command Format A 15 Figure A 19 System Configuration Query Response Format A 15 Figure A 20 First System Configuration Query Response Data Format A 16 Figure A 21 Second System C...

Страница 43: ...THIS PAGE LEFT BLANK INTENTIONALLY Figure A 1 Standard Protocol Description RS 232 Sheet A 2 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 44: ...Figure A 2 AVL 1 Communication Mode Jumper Location Standard Protocol Description RS 232 Sheet A 3 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 45: ...s stored at the file address The control panel can therefore supervise the serial port and the AVL 1 by receiving and processing the response for each transmitted command CAUTION Always transmit complete commands The AVL 1 re synchronizes on both the start and stop word Protocol Description The Notifier communication protocol provides eight features 1 Start a file playing 2 Stop a file playing 3 A...

Страница 46: ...umber from 0000 Hex to FFFF Hex The checksum is the sum in Hex of the ASCII codes in Hex of the function and file bytes After the AVL 1 receives the stop command it transmits a command acknowledgment back to the master device The command acknowledgment is one of three types acknowledge ACK not acknowledge NAK or cancel CAN The AVL 1 transmits an acknowledge ACK if the received command is in the pr...

Страница 47: ...Standard Protocol Description RS 232 Sheet A 6 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 48: ...Standard Protocol Description RS 232 Sheet A 7 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 49: ...Standard Protocol Description RS 232 Sheet A 8 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 50: ...e status response is one of two types the file status or not acknowledge NAK The AVL 1 transmits the file status if the received command is in the proper format the file number is valid and the checksum is correct The AVL 1 transmits a not acknowledge NAK if the received command is not in the proper format the file number is invalid the checksum is incorrect or one or more bytes have a parity erro...

Страница 51: ...Standard Protocol Description RS 232 Sheet A 10 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 52: ...Standard Protocol Description RS 232 Sheet A 11 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 53: ...Standard Protocol Description RS 232 Sheet A 12 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 54: ...Standard Protocol Description RS 232 Sheet A 13 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 55: ...error or framing error The system configuration response is twenty six bytes The format of the response is shown in Figure A 19 The response consists of one start byte one function byte three system configuration query code bytes sixteen data bytes four response checksum bytes and one stop byte The function byte is The system configuration query code bytes are SYS The sixteen data bytes contain in...

Страница 56: ...Standard Protocol Description RS 232 Sheet A 15 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 57: ...Standard Protocol Description RS 232 Sheet A 16 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 58: ... AVL EM Installation Field Description FF No AVL EM s Installed FE One AVL EM Installed FC Two AVL EM s Installed F8 Three AVL EM s Installed F0 Four AVL EM s Installed E0 Five AVL EM s Installed C0 Six AVL EM s Installed 80 Seven AVL EM s Installed 00 Eight AVL EM s Installed All Others Not Used Figure A 23 EM Installation Field Legend Standard Protocol Description RS 232 Sheet A 17 of A 28 Rev A...

Страница 59: ...not acknowledge NAK if the received command is not in the proper format the trouble query code is incorrect the command checksum is incorrect or one or more bytes have a parity error or framing error The trouble response is twenty six bytes The format of the response is shown in Figure A 26 The response consists of one start byte one function byte three trouble query code bytes sixteen data bytes ...

Страница 60: ...Standard Protocol Description RS 232 Sheet A 19 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 61: ...Standard Protocol Description RS 232 Sheet A 20 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 62: ...0001 to 0008 34 Message Memory I C s EPROM s Only Not Inserted in Correct Sequence N A 0000 35 Incomplete File Number of File With Error 0001 to 0999 36 Message Memory I C EPROM or PSRAM Not Blank Number of Message Memory I C Which is Not Blank 0001 to 0008 37 Message Memory I C s EPROM or PSRAM s Not Programming Correctly N A 0000 41 Input EOL Resistor Not Present Number of Input With Missing End...

Страница 63: ...Standard Protocol Description RS 232 Sheet A 22 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 64: ...the command checksum is correct the file number is an inactive file the file s status was previously checked but the data is not being written into the EPROM s properly Download File Data To download file data the master device transmits a download file data command to the AVL 1 After reception of the download file data command the AVL 1 transmits a command acknowledgment to the master device A da...

Страница 65: ...Standard Protocol Description RS 232 Sheet A 24 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 66: ...Standard Protocol Description RS 232 Sheet A 25 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 67: ...uration To download the system configuration the master device transmits a download system configuration command with the system configuration data to the AVL 1 After reception of the download system configuration command the AVL 1 transmits a command acknowledgment to the master device A data flow diagram for the sequence is shown in Figure A 37 The download system configuration command is a four...

Страница 68: ...Standard Protocol Description RS 232 Sheet A 27 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 69: ...Standard Protocol Description RS 232 Sheet A 28 of A 28 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 70: ...www PDF Zoo com firealarmresources com ...

Страница 71: ...d signal to the AMG 1 The AMG 1 shall then enter the page mode Voice messages from the AVL 1 shall be preceded by a 20 second alert signal to allow time for speaker activation An audio cassette tape is provided with each unit The cassette tape has the following tones recorded 1 Wail 2 Fast Whoop 3 High Low 4 Slow Whoop 5 Code 3 Horn 6 1000 Hz Steady Tone 7 Chime 1 chime tone every 5 seconds for 20...

Страница 72: ...ce L1D27 has the same address label 001 the message on the AVL 1 will stop playing and clear even though L1D1 on node 20 is still in a valid alarm state Extreme care must be taken to have each message label address identified to a unique device on a single node Any redundancy in label address can cause a device to be cleared by another node Speaker activation and channel selection is a function of...

Страница 73: ... 1 is selected by placing the communication mode jumper JP1 in the B position See Figure A 2 for jumper location and A B position identification on the AVL 1 printed wiring board CHART 1 AVL 1 COLOR AMG P6 SYSTEM COMMON BLUE PIN 6 TB 4 TERM 5 WHITE PIN 5 TB 1 TERM 5 RED PIN 4 SYSTEM COMMON GREEN PIN 3 TB 1 TERM 3 BROWN PIN 2 NO CONNECTION PIN 1 On AVL 1 connect TERM 6 of TB 4 TERM 4 of TB 1 CHART ...

Страница 74: ...selected by placing the communication mode jumper JP1 in the B position See Figure A 2 for jumper location and A B position identification on the AVL 1 printed wiring board CHART 1 AVL 1 COLOR AMG P6 SYSTEM COMMON BLUE PIN 6 TB 4 TERM 5 WHITE PIN 5 TB 1 TERM 5 RED PIN 4 SYSTEM COMMON GREEN PIN 3 TB 1 TERM 3 BROWN PIN 2 NO CONNECTION PIN 1 On AVL 1 connect TERM 6 of TB 4 TERM 4 of TB 1 CHART 1 and ...

Страница 75: ...ected by placing the communication mode jumper JP1 in the B position See Figure A 2 for jumper location and A B position identification on the AVL 1 printed wiring board CHART 1 AVL 1 COLOR AMG P6 SYSTEM COMMON BLUE PIN 6 TB 4 TERM 5 WHITE PIN 5 TB 1 TERM 5 RED PIN 4 SYSTEM COMMON GREEN PIN 3 TB 1 TERM 3 BROWN PIN 2 NO CONNECTION PIN 1 On AVL 1 connect TERM 6 of TB 4 TERM 4 of TB 1 and CHART 1 TER...

Страница 76: ... 2 Enter Password C 2 Main Menu C 3 Setup C 4 Program File C 6 Play File C 11 Transfer File C 12 Maintenance C 15 Diagnostics C 16 List of Figures Figure C 1 File Data Legend C 17 P83382 Display and Keypad Operation Sheet C 1 of C 19 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 77: ...nd a file is activated to play by a contact closure or a serial port command the function the operator is performing will stop and the play file number screen will be displayed When multiple messages are activated the screen will display the last file number which has started playing through any of the output channels When all messages have stopped playing the password screen will be displayed Ini...

Страница 78: ... SELECT Setup Option Screen PROGRAM FILE SCROLL SELECT Program File Option Screen PLAY FILE SCROLL SELECT Play File Option Screen TRANSFER FILE SCROLL SELECT Transfer File Option Screen MAINTENANCE SCROLL SELECT Maintenance Option Screen DIAGNOSTICS SCROLL SELECT Diagnostics Option Screen While scrolling through the six main menu selections only the and keys on the keypad are active Pressing any o...

Страница 79: ...change the password Pressing the key anytime while in the setup menu or a setup function will cause the Series AVL 1 to stop what it is doing and the main menu setup option screen will be displayed Change Password When change password is selected the following message will be displayed CHANGE PASSWORD NEW PASSWORD The operator must then enter the new password The new password must be a number betw...

Страница 80: ...ut The input number must be between 0 and 256 As the numbers on the keypad are pressed they will be displayed When the desired input number is displayed the key must be pressed to enter the input number If the input number entered is not valid or has already been selected to be the reset input the contact acknowledge enter contact number screen will remain displayed with the input number displayed...

Страница 81: ...mber between 1 and 999 which indicates the file that was selected to be recorded but already exists Pressing the key stops the program mode and the main menu program file option screen will be displayed saving the existing file Pressing the key erases the existing file and programming continues normally If the file number entered is a new file or an existing file is erased the following message wi...

Страница 82: ...message will be displayed RECORD MODE 1 START RECORDING Pressing the 1 key starts the recording When the recording is started the following message will be displayed RECORDING SEC 1 END LEFT In the screen above the represents the number of seconds of record time left in all of memory The number of seconds left will be between 0 and 960 Pressing the 1 key stops the recording and the program file me...

Страница 83: ...ng of consecutive messages on the same output channel The operator must then enter the primary output channel number through which the file is to be played The output channel number must be between 1 and 4 As a number on the keypad is pressed it will be displayed When the desired output channel number is displayed the key must be pressed to enter the output channel number After the primary output ...

Страница 84: ...e file number entered does not exist or is a telephone string file the following message will be displayed FILE NOT VALID NOT ADDED TO STRING In the screen above the represents the file number that was entered but does not exist The message will remain on the display for five seconds After five seconds the string file menu screen will be displayed If the file entered does exist and is not a teleph...

Страница 85: ...ded to the string If the common repeat is selected the following message will be displayed STRING MODE cREPEAT HOW MANY The operator must then enter the number of times that the next file number that is added to the string is going to play The numbers must be between 1 and 999 As the operator presses keys on the keypad they will be displayed When the desired number is displayed the key must be pre...

Страница 86: ...e numbers on the keypad are pressed they will be displayed When the desired file number is displayed the key must be pressed to enter the file number After the file number is entered the Series AVL 1 automatically checks to make sure it is a valid file If the file number is valid the file will be selected to play and the following play file number screen will be displayed PLAY MODE PLAYING FILE In...

Страница 87: ...d initiating a download of the system configuration and the CAB P cable between the two panels is properly in place the configuration is downloaded and the main menu transfer file screen will be displayed If the 1 key is depressed initiating the download of a message file and the CAB P cable between the two panels is properly in place the following transfer file option menu screen will be displaye...

Страница 88: ...ferred This message will remain on the display for four seconds After the four second time period the transfer file enter file number screen will be displayed If no message has been programmed into the file number selected the following file number does not exist screen will be displayed FILE DOES NOT EXIST In the screen above the represents a number between 1 and 999 that indicates the file that ...

Страница 89: ...e transfer failure screen will be displayed FILE TRANSFER FAILURE In the screen above the represents a number between 1 and 999 that indicates the file that was being downloaded when the failure took place The message will remain on the display until the key is pressed The main menu transfer file option screen will be the next screen displayed Turn off power to the destination panel for at least t...

Страница 90: ...essing the 2 key erases all files Erase A File When erase a file is selected the following erase file enter file number screen will be displayed ERASE FILE ENTER FILE The operator must then enter a file number between 1 and 999 As the numbers on the keypad are pressed they will be displayed When the desired file number is displayed the key must be pressed to enter the file number After the file nu...

Страница 91: ...ons exist then the following message will be displayed DIAGNOSTICS NO TROUBLES If a trouble condition exists then the following message will be displayed ERROR CODE xxxxxxxxxxxxxxx In the screen above the represents a two digit error code and xxxxxxxxxxxxxxx is a text phrase describing the error Table 3 lists all of the error codes and their descriptions from most significant top to least signific...

Страница 92: ... blank PSRAM I C is detected in indicated position which should have a blank PSRAM I C 37 PSRAM PROGRAMMING PSRAM I C s are not being programmed properly 41 NO EOL RESISTOR An end of line resistor is missing from an input 42 AVL EM PROBLEM A previously installed AVL EM is no longer being detected 51 BAD CHANNEL 2 The supervisory tone and peak detection for the indicated channel is not detected 52 ...

Страница 93: ...low a logic 0 the file is active Bits 1 thru 7 of the page number field contain the page number of the location of the file The address of the file must be between 8000 Hex and FFFF Hex Therefore the address MSB fields must be between 80 Hex and FF Hex and the address LSB fields can be any value from 00 Hex to FF Hex Bit 7 of the address MSB field is also used to indicate a disabled file If bit 7 ...

Страница 94: ...Figure C 1 Field Data Legend Display and Keypad Operation Sheet C 19 of C 19 Rev A July 1996 www PDF Zoo com firealarmresources com ...

Страница 95: ...www PDF Zoo com firealarmresources com ...