Document No. DFU3540000 Rev 2 

Errors and omissions excepted 

Page 1 of 2

 

BF354 

EN54-13 Sounder PCB 

 

It is assumed this product will be installed by a technically competent person who is fully conversant with 
the full Installation & Maintenance Manual for the CFP range of fire alarm panels. 

Function 

 

The EN54-13 Sounder PCB (shown right) provides two sounder circuits 
for the CFP fire alarm panel that are fully compliant with EN54-13 
(Compatibility Assessment of System Components). 
Each sounder circuit has to be fitted with an Active end-of-line Device 
(EOLD). 
 

Items Supplied 

 

1 x EN54-13 Sounder PCB (Part No. BF354) – shown right (above) 
2 x Active EOLD (Part No. BF355) – shown right (below) 
1 x 2-way polarised power supply loom 
1 x 10K resistor 
2 x retaining screws 
 

Installation 

 

Note the Sounder PCB has to be mounted inside the CFP enclosure. 
Always remember to power down the system before fitting the Sounder PCB. 

Step 1.

 

Isolate Mains supply to the CFP panel and disconnect the panel’s battery back-up supply. 

Step 2.

 

Remove the Main Control PCB from the CFP panel (note that the connection cable needs to 
be disconnected from PL1 on the Power Supply PCB). See Fig.1. 

Step 3.

 

Locate the two mounting slots provided in the base of the CFP panel, then slide the Sounder 
PCB downwards into position and secure with two retaining screws (provided). See Fig.1. 

Step 4.

 

Wire  the  2-way  polarised  loom  (supplied)  from  PL1  on  the  Sounder  PCB  to  PL2  on  the 
Power Supply PCB. See Fig. 1. 

 

Fig. 1 – Location of Panel’s Base PCBs and Removal Details 