Errors and omissions excepted 

Document No. DFU3540000 Rev 2

 

Step 5.

 

Wire the conventional sounder circuit(s) to the Sounder PCB terminals (Sounder Out Circuit 
1 & Sounder Out Circuit 2). See Fig. 2. 

Step 6.

 

Wire  the  Active  EOLD  (supplied)  to  the  last  sounder  on  each  circuit,  as  shown  in  Fig.  2 
below. Note if sounder circuits are not connected, the Active EOLD must still be fitted at the 
Sounder PCB terminals. 

 

Fig. 2 – Sounder Circuit Connections 

 

Step 7.

 

Terminate the sounder circuit’s screens at the panel’s base earth post. See Fig. 3. 

 

Fig. 3 – Earthing Screens to Base Earth Post 

 

Step 8.

 

Wire the Sounder PCB to the Main Control PCB and fit 10K resistor (supplied). See Fig 4. 

 

Fig. 4 – Sounder PCB to Main Control PCB Connections 

 

Step 9.

 

Refit the Main Control PCB in the CFP panel. 

Step 10.

 

Reconnect Mains and battery supply to the CFP panel. 

Step 11.

 

Test the sounder circuits for correct operation. 

 

Technical Specification 

Description / Part Number: 

EN54-13 Sounder PCB / BF354 

Number of Sounder Circuits: 

EOLD Value: 

6800 ohms, 5% tolerance, 0.25W. 

EOLD Monitoring: 

Detects series resistances down to 10

Ω

 

±

 10%. 

Sounder Circuit Monitoring: 

Monitored for partial and full, open or short circuit faults. 

Alarm Voltage: 

27VDC maximum, 20VDC minimum. 

Sounder Circuit Fuses: 

Each circuit fused at 400mA hold current, 800mA max. trip current. 

Total Sounder Output Current: 

2 x 400mA = 800mA. 

Maximum Number of Sounders: 

Dependant on type of sounder, see EN54-13 Model. 

 

DO NOT connect any sounder 
circuits to CFP terminals  
SC1, SC2, SC3 & SC4. 