E3M080 Line module ”Collective”
97
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
6
Fuse: 'F17' 1 A/F Module supply (SMD fuse, can only be changed at fac-
tory)
7
Programming switch "S4": Allows the line short circuit to be evaluated either
as fault or alarm(common to all 8 lines)
ON
=
Short circuit evaluated as alarm (AI pulse generator active)
S4-2
OFF = Short
circuit
evaluated as fault
S4-1
= no
function
S4-2 = set to "off" at the factory
22.7 Connections
Max. 25 coll. DS11 detectors
MS6, MS7, MS9, MS24 depending of detector type, see docu 825
Line type 11 = Transzorb 20V
1 = EOL22 (Ex)
Line type 11 or 1
to emergency operation link E3G110
- open collector per line for ext. LED
- active upon emergency alarm
Mimic display
Flat cable header (Mini)
ST10
to other I-Bus modules
Data communication
I-Bus modules
Double flat cable header
ST1
red
green
blue
blue
Supply
I-Bus modules
Plug-in terminals
K1
from previous I-Bus modules
Line 8
Line 7
Line 6
Line 5
unused
(connect to chassis ground)
Module chassis ground
unused
Line 4
Line 3
Line 2
Line 1
Terminal block
X20
E3M080
1
2
3
4
5
6
7
8
9
10
11
12
+
-
+
-
+
-
+
-
13
14
15
16
+
-
+
-
17
18
19
20
+
-
+
-
F2
F1
F4
F3
F6
F5
F8
F7
F10
F9
F12
F11
F14
F13
F16
F15
SB2
2
3
4
+
+
1
24V
5V
Ex detector
EOL22 (Ex)
Explosion hazard area
SB3
Ex detector
DC1192
EOL22 (Ex)
1) 2)
2)
Line type 3
Line type 11 or 1
3)
3)
*
*
*
to other I-Bus modules
from previous I-Bus modules
Explosion hazard area
Z-diode
5.6V
Z-diode
5.6V
Z-diode
5.6V
alarm contact
*
resistor 1.2k
Ω
or
4)
GND
-
-
Transzorb 20V
Transzorb 20V
Transzorb 20V
Transzorb 20V
Pin assignment ST10
Pin
Line
GND
GND
GND
GND
1
2
3 4
5
6
7
8
9 10 11 12
1
2
3 4
5
6
7
8
*
26
Pi
n
26 Pin
12
Pi
n
24VDC
1) No detectors may be connected in front of the safety barrier (SB2). This application is without limitation only once permissible per control
unit and in installation with E3X.. / E3G070 only if the earth leak detection is set to 'inactive' (further details see page 95)
2) Details regarding max. admissible line resistance see document 1204
3) Local ground connection
4) To read in technical alarms. Do not mix with detectors on the same line.