B3Q4.. / 560 Control terminal AlgoPilot
176
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
42.8 Connections
B3Q4..
Inputs TROUBLE
power supply
(default = not active)
Local power supply
(internal only)
1
2
3
4
1
Plug-in terminals ”black”
K2
3
2
1
+
+
Plug-in terminals ”orange”
K1
24V
5V
Supply
I-Bus modules
To the I-Bus modules
Emerg. power
Power supply
Battery
C
External key switch
only supported with control unit software ’EP4’ (V4.4x) onwards
1
2
1
Plug-in terminals ”orange”
K4
Operat. enabled
C
External operation
enabled
1
2
3
4
1
Plug-in terminals ”grey”
K5
C-Bus
B1
A1
B2
A2
1
2
3
4
1
Plug-in terminals ”orange”
K6
Emergency
operation
5
24V
45V OUT
0V
F3
Fire alarm
F4
Switch off horn
1
2
3
4
5
6
+
-
+
-
Plug-in terminals ”orange”
K7
F2
F1
3
2
8
9
10 14 15
+
-
-
+
E3X10.
Possibly additional control
terminals B3Q...
4
Supply 1
Supply 2
Terminal block
X16
4
-
12
13
7
6
2)
blue
blue
green
red
4)
serves at the same time as supply imput for the ”CI”
B3Q4..
GND
-
-
3)
1) 5)
6)
1) C-Bus must always be wired as a loop line (even with built-in control terminal AlgoPilot B3Q...)
2) Jumper must always be inserted
3) Configuration as in-/or output see jumpers X31, X32, X33, X34, Y31, Y32, Y33, Y34 on page 173 and 23
4) For application as "CI", external control terminals ("CT") are connected on K7
5) Cabling C-bus:
max. 1000m per loop with Ø 0.6 mm wire
max. 1400m per loop with Ø 0.8 mm wire
(always including return line) for cable type (impedance adaptation) see page 173
6) "Cabling principle AlgoPilot B3Q..." –> see page 23