INSTALLATION INSTRUCTIONS

 

www.wheelockinc.com 

   

SERIES RSS AND RSSP MULTI-CANDELA STROBE APPLIANCES

 

(WALL MOUNT VERSIONS) 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

Wheelock’s Series RSS and RSSP Multi-Candela Strobes can provide a non-synchronized strobe appliance when connected directly to a fire alarm control panel 
(FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or a Wheelock power supply 
utilizing the Wheelock sync protocol.  The Series RSS and RSSP Multi-Candela Strobe Appliances are UL Listed under Standard 1971 (Signaling Devices for the 
Hearing Impaired) for indoor Fire Protection Service and ULC Listed under Standard CAN/ULC-S526-02 for indoor Fire Protective Service.  The Multi-Candela 
Strobe provides four selectable light output intensities in one unit.  These strobes are listed for 

wall mount

 

only

 with the backboxes specified in these instructions (see 

mounting options).  RSS models have an integrated strobe mounting plate that can be mounted to a single-gang, double-gang, 4” backbox, 100mm European backbox 
or SHBB surface backbox.  The strobes use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability 
for effective visible signaling.  All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by the FACP. 

 

 

NOTE

:  All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and 

Canadian Electrical Code, Part 1.  Final acceptance is subject to the authority having jurisdiction (AHJ). 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS 
INJURY OR DEATH TO YOU AND/OR OTHERS.

 

 

SPECIFICATIONS: 

 

Table 1:  UL/ULC Ratings 

 

Model 

Regulated 

Voltage 

(VDC/VRMS) 

Voltage Range 

Limit Per UL 1971 

(VDC/VRMS) 

Voltage Range Per 

CAN/ULC-S526-02 

(VDC/VRMS) 

Strobe 

Candela 

(cd) 

Mounting 

Options 

RSS-24MCW 24  16.0-33.0 

20.0-31.0 15/30/75/110 

A,B,C,D 

RSSP-24MCW 24 

16.0-33.0 

20.0-31.0 15/30/75/110 E,F 

 

Table  1A: Audibles/Speakers for RSSP Strobe/Plate 

Product Series 

Multitone Appliances 

AMT, MT, MT4 

Horns AH, 

NH 

Motor Bells 

MB-G6/G10 

Speakers 

ET-1010/1080, ET70, E70 

Chimes CH70 

 

NOTES: 

1.

 

Strobes will produce 1 flash per second over the "Regulated Voltage" range. 

2.

 

These strobes meet the required light distribution patterns defined in UL 1971 and ULC-S526-02. 

3.

 

All models are listed by UL/ULC for indoor use with a temperature range of +32

°

F to +120

°

F  (0

°

C to +49

°

C) and maximum humidity of 93% 

±

 2% RH.  The 

effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when  it is stored in the original cartons and is not 
subjected to misuse or abuse.   

WARNING:  CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 

 

Table 2:  Current Ratings (AMPS) 

Maximum RMS Current  

Voltage  15cd 30cd 75cd  110cd 

DC 

16-33VDC 

0.060 0.092 0.165  0.220 

FWR 

16-33VRMS 

0.102 0.155 0.253  0.347 

 

When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number 
of strobes.  Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required 
safety factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

 

 

 

CAUTION:  

These notification appliances are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as 

“Regulated.”  These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the 
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. 
 

Содержание RSS-24MCW

Страница 1: ...PER APPLICATION CANDELA SETTING INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 UL ULC Ratings Model Regulated Voltage VDC VRMS Voltage Range Limit Per UL 1971 VDC VRMS Voltage Range Per CAN ULC S526 02 VDC VRMS Strobe Candela cd Mounting Options RSS 24MCW 24 16 0...

Страница 2: ...commodate the field wires and stresses from the wires could damage the product CAUTION Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit especially if sheathed multiconductor cable or 3 4 conduit fittings are used Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommend...

Страница 3: ...tting The setting is indicated by a pointer and can be seen on the bottom side of the lens See Figures 3 and 4 below 7 Mount the SMP first to the backbox Next slide the beauty plate over the SMP until the 2 snaps of the beauty plate engage with the SMP 8 The beauty plate can be removed from the strobe assembly once engaged First gently insert a screwdriver into one of the slots located on the top ...

Страница 4: ...trical Code NEC Occupational Safety and Health Administration OSHA local state county province district federal and other applicable building and fire standards guidelines regulations laws and codes including but not limited to all appendices and amendments and the requirements of the local authority having jurisdiction AHJ Wheelock products when properly specified applied installed operated maint...

Отзывы: